Key Features and Options
• 1 to 4 control loops with TRU-TUNE+ adaptive
control algorithm for superior controllability
• 40 profiles for ramp and soak
• Ethernet Modbus® TCP connectivity
• Multiple high-speed USB host ports
• Over/under-temperature limits for safety shutdown
• Universal, thermistor and ac current measurement inputs
• Inputs and outputs expandable from 1 to 36
• SENSOR GUARD prevents unplanned process shutdowns and
product loss by switching to a backup sensor if the primary
sensor fails
• High current outputs for up to 10A heaters or other loads
• Programmable timers, counters, math and logic
• Temperature, cascade, altitude, relative humidity, compressor
algorithms and Vaisala® humidity compensation
• Sequencer start-up and control
• Retransmit and remote set point
• USB configuration port
• Configuration settings can be stored and recalled
• Removable modules and connectors
• Front-panel mount and flush mounting options
• Right angle and front-screw terminal options
• UL® listed, CSA, CE, RoHS, W.E.E.E., FM
Common Specifications
Line Voltage/Power
• Data retention upon power failure via nonvolatile memory
Functional Operating Range
• Type J: -346 to 2192°F (-210 to 1200°C)
• Type K: -454 to 2500°F (-270 to 1371°C)
• Type T: -454 to 750°F (-270 to 400°C)
• Type E: -454 to 1832°F (-270 to 1000°C)
• Type N: -454 to 2372°F (-270 to 1300°C)
• Type C: 32 to 4200°F (0 to 2315°C)
• Type D: 32 to 4200°F (0 to 2315°C)
• Type F: 32 to 2449°F (0 to 1343°C)
• Type R: -58 to 3214°F (-50 to 1767°C)
• Type S: -58 to 3214°F (-50 to 1767°C)
• Type B: 32 to 3300°F (0 to 1816°C)
• RTD (DIN): -328 to 1472°F (-200 to 800°C)
• Process: -1999 to 9999 units
Calibration Accuracy
• Calibration accuracy and sensor conformity: ±0.1% of
span, ±1°C at the calibrated ambient temperature and
rated line voltage
• Types R, S, B: ±0.2%
• Type T below -50°C: ±0.2%
• Calibration ambient temperature at 77°F ±5°F (25°C ±3°C)
• Accuracy span: 1000°F (540°C) min.
• Temperature stability: Typical ±0.1°F/°F (±0.1°C/°C) rise in
ambient max.
Configuration Diagnostics
• Indicates if modules present match the expected
configuration settings
USB Device Port (Coming soon, consult factory
for availability.)
• Version: USB 2.0 full-speed
• Connector: USB Mini Type B, 5 position
• Recognized as a mass storage device/serial
communications
• Driver for Microsoft® Windows® 7 and Windows® 8
USB Host Port
• Total of 2 available
• Version: USB 2.0 hi-speed
• Connector: USB Type A, high-retention
• Flash drive must be FAT32 file system
• Max. current 0.5A/port
System Configuration Requirements
• F4T has 6 slots for flex modules (FM)
• EIA-232/485 Modbus® RTU flex module, if used, must occupy
slot 6 location
• A maximum of two 10A SSR FM modules can be used in the F4T
and each will require space for 2 slots. Valid in slots 1. 2. 4 or 5
Wiring Termination—Touch-Safe Terminals
• Right-angle and front-screw terminal blocks for input, output
and power supply connections
• Input, output and power terminals: touch safe, removable,
12 to 30 AWG
wechat/whatsapp: