Ovation Simulation
Emerson offers Ovation Simulation solutions using virtual technology that faithfully replicates the
Ovation DCS within a simulator configuration by using a few desktop workstations.
This approach reduces hardware costs and footprint, allows easy portability for use throughout the facility,
and greatly simplifies ongoing simulator maintenance and upgrades to track ongoing control system modifications.
Ovation simulation is a valuable and flexible tool to improve plant operations.
Typical applications include DCS validation prior to its installation, operator training programs, engineering upgrades,and control changes to improve plant performance.
Specifications
Number of segments (ports)
2
Number of field devices
16 per port (dependent on device power consumption)
Number of Ff funtion blocks
96 per card (64 fieldbus and 32 standard DeltaV)
Voltage provided per segment
28-30 VDC (short circuit protected)
Current provided per segment
400 mA (short circuit protected)
Isolation
Each port is isolated from the system and from each other and factory tested to 1500 VDC.
Nominal signal range (span)
Fieldbus Foundation IEC 61158-2
LocalBus current per card (12 VDC nominal)
200 mA typical, 300 mA maximum
Heat Dissipation
7.2 W
Operating Temperature
-40 to 70 °C (-40 to 158 °F)
Storage Temperature
-40 to 85 °C (-40 to 185 °F)
Reltive Humidity
5 to 95% , non-condensing
Shock
10 g½-sine wave for 11 ms
Vibration
1 mm peak-to-peak from 5 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz

Maximize smart device capabilities. Increase your quality and throughput by taking advantage of the added diagnostics
of FOUNDATION Fieldbus I/O devices. Field device status is updated continuously using FOUNDATION Fieldbus I/O.
For multi-variable devices, all process variables are available on the single fieldbus at the cost of a single Device Signal Tag.
Redundant H1 cards provide increased availability.
The DeltaV system offers redundant H1 interfaces. The two H1
interfaces are connected with a redundant terminal block to
provide back-up link active schedule (LAS) capability that also
maintains communication with the host system.
Transfer to the standby card is automatic and requires no special configuration.
Ongoing diagnostics ensure the standby H1 card is available on demand.