Product Specifications
Function
Isolated barriers are isolators used for protection of intrinsically safe circuits in hazardous
areas. In addition to the required current, voltage and power limitation, the isolated barriers
have a galvanic isolation between the field circuit and the controller.
The K-System consists of wide range of isolated barriers suitable for mounting on 35 mm
DIN mounting rail. K-System is easy to specify, integrate and expand. Our extensive line
of intrinsic safe isolators for hazardous location applications contains over 150 different
devices.

Housing Styles
Depending on the functionality and application, K-System devices have 3 different housing
widths:
• KC devices with 12.5 mm width
• KF devices with 20 mm width
• KF devices or KHdevices with 40 mm width
The 3 housing widths versions have the same system characteristics. All devices
can be mounted on the 35 mm DINmounting rail or the Power Rail. See chapter 2.9
Terminals
Removable Terminal Blocks
The KC and KF devices have removable terminal blocks.
The removable terminal blocks simplify connection and control cabinet assembly.
The terminal blocks offer space for the connection of leads with core cross-sections
of up to 2.5 mm2 (14 AWG). The terminal blocks are coded with red coding pins
so misconnection of terminal blocks are eliminated.
Observe the tightening torque of the terminal screws. The tightening torque
is 0.5 Nmto 0.6 Nm.
The 20mm and 40mm wide KFdevices are factory-equipped with screw terminals.
The KC devices are available with screw terminals or spring terminals. The order designation
of the versions of the KC devices with spring terminals has the extension .SP.
As an alternative to the factory-equipped terminal blocks the devices can be used with other
terminal blocks:
• Terminalblocks with screw terminals
• Terminalblocks with screw terminals and test plug socket
• Terminalblocks with spring terminals and test plug socket
These terminal blocks are available as accessories. The terminal blocks can be easily coded
with KF-CP coding pins (available optionally).
Protection against direct contact
The removable terminal blocks have different heights:
• Height 15mm (1), (2), (3): These terminal blocks are used in applications that have rated
voltages lower than 50 V AC. The insulation of the removable terminal blocks provides
protection against direct contact. The insulation corresponds to a reinforced insulation
according to EN 61010-1 for a rated insulation voltage of 50 V AC.
• Height 15.5mm (4), (5): These terminal blocks are used in applications that have rated
voltages higher than 50 V AC. The insulation of the removable terminal blocks provides
protection against direct contact. The insulation corresponds to a basic insulation
according to EN 61010-1 for a rated insulation voltage of 300 V AC. The higher terminals
are X marked.