Purpose
The purpose of the Pepperl+Fuchs 6000 series Type X & Ex px, Zone 1
enclosure protection system is to allow the use of general purpose or
non-rated electrical or electronic devices located in general purpose
enclosures instead of explosionproof/flameproof, Type 7 or 9 / Ex d
enclosures or other means of protection for the rated area.
Other purposes include heat, moisture, and dust contamination
prevention.

Description
The 6000 series Type X & Ex px purge and pressurization system protects
general purpose equipment mounted in a standard enclosure.
This allows the enclosure to be located and the equipment operated in a
hazardous area.
The hazardous area classification can be Class I, Class II, Division 1 / Zone
1. Zone 21. The 6000 series operates by controlling and monitoring
compressed instrument air or inert gas through the protected enclosure(s)
so as to remove and prevent the accumulation of flammable gas, vapors,
or dust.
The 6000 series system features these main parts:
• Electronic processor (EPCU) housed in an explosionproof enclosure
• I.S. electrical/pneumatic manifold assembly
• I.S. user interface for programming and monitoring the system
• 316L stainless steel (UNS S31603) type 4X IP66 enclosure for EPCU and
connections
• Pressure relief vent with flow and pressure monitoring at the exhaust.
The user interface allows programming of up to 4 switch inputs,
temperature modules, enclosure power contacts, 2 auxiliary outputs, and
various operational functions.
Through the user interface menus, configuration of the standard information
for setup and operation of a system (purge time, flow rates, pressures,
enclosure size, etc.) are easily programmed. Additional features allow
inputs for system bypass, enclosure power on/off, temperature overload
and activation of rapid exchange flow for cooling or auxiliary relay for
separate cooling source, delay power shutdown, and more.
The two auxiliary contact outputs can be configured to activate on most
of the input switches or any of the configured alarm states for pressure,
flows, and temperature.
The power for the solenoid valve on the manifold unit, inputs, the user
interface controller (UIC), and EPV-6000 vent are provided by the EPCU
through the internal galvanically isolated intrinsic safety barrier.
No additional I.S. barrier is required.
The adjustable mounting bracket and the universally mountable vent
make the 6000 system easy to install horizontally or vertically onto the
enclosure. A component kit is available for custom installations that fit
specific customer needs.
The 6000 control unit can monitor multiple enclosures and control and
accept inputs from two (2) EPV-6000 vents.
The 6000 series provides a complete system for purging and pressurizing
enclosures for hazardous location operation.