DPU Front Panel Input/Output Connections
Overview
All input/output connections are contained on the front DPU chassis panel.
The chassis contains:
• Two 10/100 Ethernet ports
• One Backup Link Port
• One Serial Port (Optional)
• One IRIG-B Interface Port (Optional)
This chapter describes each link in some detail.

Ethernet Network Connections
The DPU chassis contains two 10/100 Ethernet ports using RJ-45 connectors
to interface with the maxNET communication network. Network A and
Network B operate as independent networks. Because the Ethernet channels
are independent, a fault on one network or processor will not affect the
operation of the other, or cause a DPU failover. Ethernet messages are
sent/received based upon the DPU’s Ethernet address with minimal control
processor intervention.
Configuring the Ethernet Switch
Each DPU connects to the maxNET through two Ethernet switches – one for
Network A and one for Network B. The Ethernet switch ports that connect to
DPUs should be configured for 10Mbps or 100Mbpsfull-duplex operation.
Auto-Negotiate is also supported but not the preferred setting. Switch ports
that connect to other switches should be configured for 100Mbps or
1.000Mbps full-duplex operation. Refer to the user manuals that came with
your Ethernet switch to learn how to change the port settings.
Note: When using the Cisco Catalyst 2950 Ethernet Switches, the switch and
DPU should be set to Auto-Negotiate.
Backup Link
A 100 Mbps Ethernet link is used to pass database information between an
active DPU and an inactive standby DPU. A custom Category 5e cable
(Metso #050292) connects the DPU backup pair together via the backup
link’s RJ-45 connector. Secondary DPUs will typically be installed in the
lower chassis just below the primary DPUs.
Serial Port
The DPU front panel contains a serial port utilizing an 8-pin RJ45 style
connector.
Table 2-1 provides the pin-outs for the 8-pin port. The signal levels are
standard RS232.
The serial port supports redundancy when a backup pair of DPUs is used.
The serial port is only operational if the DPU is “Active”. The RS232
drivers on the “Inactive” DPU are turned off. The use of this feature requires
a redundancy cable to connect between the two DPUs and the RS232 device.
(Metso Automation # 050355). This cable has an RJ45 for each DPU and a
common DB9 connector with male pins.

IRIG-B Interface Port (Optional)
The DPU front panel optionally contains an IRIG-B ports for connecting to
an external time source. The connector is a BNC and is transformer coupled
on the DPU. See Chapter 8 for more details.