Product Overview
CENTUM CS 3000 is Yokogawa large‑scale distributed control system(DCS), evolved from the medium‑size CENTUM CS1000. documented in Yokogawa technical report rd‑tr‑r00028‑001 (No.28. 1999).
CS3000 follows Yokogawa’s ETS (Enterprise Technology Solutions) strategy. Its core design philosophy: Human‑interface stations(HIS) run on open Windows‑NT OS with commodity PC hardware; Field Control Stations(FCS) use proprietary real‑time OS for 24/7 mission‑critical plant control. Control network V‑NET is physically separated from office Ethernet to balance openness and real‑time reliability for process industries such as petrochemical, chemical, power, pulp‑and‑paper.

System Scale
| Parameter | Value |
|---|---|
| Max stations per domain | 64 |
| Total maximum stations whole‑system | 256 |
| Maximum process tags | 100 000 |
CENTUM Product Family History
1. 1975: Original CENTUM — world‑class early DCS, separate HMI‑controller architecture
2. 1983: CENTUM‑V; 1988: CENTUM‑XL, 32‑bit proprietary closed‑system
3. 1993: CENTUM‑CS, partial UNIX‑based open‑architecture
4. 1997: CENTUM CS1000 for small‑medium plants (Windows‑NT HMI)
5. 1998: CENTUM CS3000 for large‑scale plants
Main Hardware Components
HIS (Human‑Interface Station)
Operator & engineering station running Windows‑NT OS. Two hardware options:
1. Commodity general‑purpose PC: Cost‑effective, user‑selectable hardware.
2. Yokogawa Console: Industrial touch console, preserves classic DCS operator workflow.
> HIS can execute both DCS monitoring & configuration, plus general Windows business software such as MS Excel.
FCS (Field Control Station, control core)
FCS executes real‑time plant control and does NOT run Windows NT. It uses Yokogawa proprietary real‑time operating system for uninterrupted 24‑hours‑a‑day plant operation. Two variants:
1. LFCS (Standard FCS): Large capacity, inherited hardware & logic from CENTUM‑CS.
2. SFCS (Compact FCS): Compact, smaller capacity, based on PFCS proven hardware.
Network & Gateway Units
1. V‑NET: Dual‑redundant 10 Mbps token‑passing control bus for real‑time control traffic between FCS / HIS. Isolated from office Ethernet.
2. Ethernet: Information‑level network for MES / ERP / third‑party host connection.
3. ACG: Gateway converting V‑NET to Ethernet TCP/IP protocol.
4. BCV series gateway:
- BCV‑V: Interconnect multiple CS3000 domains
- BCV‑H / BCV‑L: Gateway for legacy CENTUM‑XL system migration
5. ExaOpc Station: OPC‑server unit providing DCS process‑data to upper‑level enterprise‑systems.
> Related spare note: PW501 / PW502 / PW504 are power‑supply modules for CS3000 FCS rack. PW501:100‑120 V AC input; PW502:220‑240 V AC; PW504:24 V DC.
Key Software & Functional Features
Operation & Monitoring
- Two screen modes: Window‑mode (co‑exist with other Windows applications) / Full‑screen‑mode (classic DCS operator experience).
- Long‑term data archiving, enhanced graphic container & gradient graphic function.
Engineering & Off‑line Simulation
1. Virtual‑Test simulation: Test FCS control logic on PC without real hardware.
2. Divided‑Engineering: Partial project import, online merge into running system; expand plant without shutdown.
3. Quick online modification via fixed‑word‑length database.
4. Import / export engineering data with Microsoft Excel format.
Communication & Interoperability
1. Industry‑standard OPC Server for MES / third‑party system data access.
2. Active‑X embedding inside operator graphic displays.
3. Field‑bus support: FOUNDATION Fieldbus, PROFIBUS; mixed conventional analog I/O and field‑bus devices.
4. Ethernet interface for data exchange with multi‑brand PLCs.
Batch Control
CS Batch3000. fully compliant with ISA‑SP88(IEC) batch‑process standard, pre‑built templates shorten batch‑project commissioning.
Open‑Architecture & Migration Capabilities
1. Re‑use existing CENTUM‑V / CENTUM‑XL I/O hardware; only upgrade controller while legacy control logic keeps running.
2. Seamless integration with ProSafe‑RS safety instrumented system(SIS).
3. Interfaces with Exaquantum plant information management platform, bridging DCS and MES layer.
Typical Application Industries
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com