The ELX4154 analog output terminal is used for the direct connection of
intrinsically safe field devices located in hazardous areas classified zone
0/20 or 1/21. It can be used, for example, to control intrinsically safe
controllers for control valves. The output current range can be switched
between 0…20 mA and 4…20 mA.

EtherCAT terminals of the ELX series must always be operated in
conjunction with the ELX9560 power supply terminal. This terminal
generates an electrically isolated output voltage (24 V EX) from the input
voltage (24 V DC) for supplying the subsequent ELX terminals.
If a new power supply is required, the combination of an ELX9410 and
an ELX9560 can be used so that further ELX terminals can be added.
The ELX terminal segment must be terminated with one ELX9012. two
ELX9410 or one EK1110. The use of two ELX9410 allows the use of EL
terminals behind ELX terminals. With the EK1110. the terminal segment
can be continued via an EtherCAT cable, for example to implement cable
redundancy.