MicroNet controls require a fixed wiring installation for ac applications. Ground leakage exceeds 3.5 mA
AC. Maximum ground leakage for ac installations is 7.2 mA at 60 Hz. A ground conductor connected to
the chassis is required for safety. The power supply grounding terminal(s) should also be connected to
earth to ensure grounding of the power supply printed circuit boards. The grounding conductor must be
the same size as the main supply conductors.
Branch circuit fuses, circuit breakers, and wiring must meet appropriate codes and authorities having
jurisdiction for the specific country (CE, UL, etc.). See Table 4-4 for maximum recommended fuse or
breaker ratings. Do not connect more than one main power supply to any one fuse or circuit breaker. Use
only the wire sizes specified in Table 4-4 which meet local code requirements. Time delay fuses or circuit
breakers must be used to prevent nuisance trips.
Power requirements depend on the number and type of modules supplied for each system. For a system
with a single I/O chassis, size the input power source according to the rating of the MicroNet power
supply to which the source is connected. Do not size the supply mains for the sum of the MicroNet power
supply ratings when redundant supplies are used. MicroNet supplies are redundant when installed in the
same chassis. Redundant supplies share the load between them equally, but each must provide for full
load in the event that one of the units is disabled. Table 4-4 gives the maximum overload protection for
supply mains connected to any single or redundant pair of MicroNet main power supplies. It is not
recommended that both MicroNet main power supplies of a redundant pair be connected to a single
source, since failure of that source would disable the system.
Woodward Discrete Input - 16 Channel 8200-1104
Woodward Discrete Output - 16 Channel 8200-1105
Woodward Termination Resistor Kit 8923-1889
Woodward Dataforth I/O Thermocouple - K-Type 1784-1028
Woodward Dataforth I/O RTD - 100 Ohm 1784-655
Woodward Dataforth I/O 4-20 mA Input 1784-659
Woodward Table A. NetCon Analog Cables 12 feet, Black 5416-349
Woodward Table A. NetCon Analog Cables 14 feet, Black 5416-350
Woodward Table A. NetCon Analog Cables 16 feet, Black 5416-351
Woodward Dataforth I/O 0-5 VDC Input 1784-657
Woodward Network Switches Ethernet - 8 Port, RJ45 Connectors 1711-1350
User name | Member Level | Quantity | Specification | Purchase Date |
---|
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved