Model Type: AIN220 Analog Input Base - Harmony Block I/O
Accuracy
Time synchronization accuracy of the Server is valid when the Server is in time
synchronization mode. The options are:
• Low accuracy (lowest accuracy); priority 0.
• Low accuracy battery backed; priority 3.
• High accuracy battery backed; priority 6.
• IIOIS20 node; priority 9.
• IIOIS20 SCSI; priority 10.
• PIMS SCSI; priority 11.
• Satellite clock system (highest accuracy); priority 12.
These accuracy settings are only used when negotiating for time mastership with
other nodes in the underlying Harmony control network.
Master Update Period
Master update period is the frequency that Harmony Server synchronizes time with
the underlying Harmony control network. This property is used only when Time
Synchronization is enabled. The permissible values are 120 to 3540 seconds.
Message Wait Period
Message wait period is the Period that Harmony Server waits before attempting to
assume time mastership on the control network. This property is used only when
Time Synchronization is enabled. The permissible values are between 180 and 3660
seconds. Additionally, the configured value must greater than the Master Update
Period.