SOE SPECIFICATION
Module Event Buffer
• 480 Events+32 Overflow
Event Recording peak rate, module
• 64000 events/sec
Duration of peak rate
• 7.5 ms (max) for 32 SOE channels enabled
Event Recording continuous rate, module
• 220 events/sec (min)
Each of 32 inputs
• 6.8 events/sec (min)
Excessive Event Threshold (for 32 inputs)
• 150 events/sec (for each channel)
SOE Module time stamping resolution
• 125 μS
System Time Stamping resolution
• 250 μS
Simultaneous Inputs, Time Stamping error
• Within one module – 0.25 ms (max)
• Within one 8000 Node – 1.0 ms (max)
• Between 8000 Nodes – 5.0 ms (typ)
The Control System
Each downloaded application is a complete distributed application running on the target controller.
Multiple applications, running on separate controllers, can be linked together using the peer-topeer tool,
which identifies tagnames for use across the network.
This data exchange mechanism provides a very efficient way of sharing information between multiple controllers.
• 16 single-ended input channels
• Intrinsically safe field circuits
• Simple apparatus, dry contacts
or IS proximity detectors
• Open and short-circuit
field wiring detection
Project backup and restore
You can create a backup file of your project at any time.
This useful feature enables you to save your application in a known state, and if necessary, restore the project to that state.
You can import and export resources from one project to another, enabling you to re-use prior work.
If the results of importing or exporting resources are unsatisfactory, you can choose to restore the project.
Downloader The Workbench
Downloader is used to download the firmware and control strategy to the controller.
With Redundant Controllers, strategy changes can be downloaded to a backup controller without disrupting control in the primary controller.
When the download is complete, the backup controller will take over control and update the primary controller with the changes.
Control can revert back to the primary controller after these changes are incorporated.
Downloading to a simplex controller can be done on-line and without initializing data, the new strategy starting on the next execution cycle.
GE | 8811-IO-DC | 8811-IO-DC 8-Channel Safety DI/DO, 24VDC, module-powered |
GE | 8118-DO-AC | 8118-DO-AC 8-channel DO, 20-250Vac isolated, unpowered |
GE | 8201-HI-IS | 8201-HI-IS 8-channel Intrinsically Safe Analog Input, 4-20mA with Hart |
GE | 8206-TI-IS | 8206-TI-IS 8-channel Intrinsically Safe RTD input |
GE | 8202-HO-IS | 8202-HO-IS 8-channel Intrinsically Safe Analog Output, 4-20 mA with Hart |
GE | 8215-DO-IS | 8215-DO-IS 4-channel Intrinsically Safe Digital Output, solenoid driver IIC gas groups |
GE | 8204-AO-IS | 8204-AO-IS 8-channel Intrinsically Safe Analog Output, 4-20 mA |
GE | 8220-DI-IS | 8220-DI-IS 16-channel Intrinsically Safe Digital Input, switch/promixmity detector |
GE | 8205-TI-IS | 8205-TI-IS 8-channel Intrinsically Safe THC/mV input |
GE | 8601-FT-NI | 8601-FT-NI Field terminal, non-incendive (Div 2) |
GE | 8617-FT-NI | 8617-FT-NI Field Terminal, non-incendive, for 16 ch DI |
GE | 8602-FT-ST | 8602-FT-ST Field terminal, standard |
GE | 8618-FT-MT | 8618-FT-MT 16-pin Mass Termination Assembly (Div 2) |
GE | 8603-FT-FU | 8603-FT-FU Field terminal, non-incendive, fused (Div 2) |
GE | 8619-FT-MT | 8619-FT-MT 44-pin Mass Termination Assembly (Div 2) |
GE | 8604-FT-FU | 8604-FT-FU Field terminal, fused |
GE | 8620-FT-MT | 8620-FT-MT Field terminal assembly |
GE | 8605-FT-TC | 8605-FT-TC Field terminal, thermocouple |
GE | 8621-FT-IS | 8621-FT-IS Intrinsically Safe Field terminal, standard |
GE | 8606-FT-RT | 8606-FT-RT Field terminal, RTD |
GE | 8622-FT-IS | 8622-FT-IS Intrinsically Safe Field terminal, loop-disconnect (not for 8 channel DI) |
GE | 8607-FT-TC | 8607-FT-TC Field terminal, 8-channel with T/C |
User name | Member Level | Quantity | Specification | Purchase Date |
---|
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved