The power supplies can only be installed into slots PS1 (power supply #1) and PS2 (power supply #2). If
redundant power supplies are not needed, blanking plates must be installed in the slots not being used.
Branch circuit fuses, circuit breakers, and wiring must meet appropriate codes and authorities having
jurisdiction for the specific country (CE, UL, etc.). See Table 4-3 for maximum recommended fuse or
breaker ratings. Do not connect more than one main power supply to any one fuse or circuit breaker. Use
only the wire sizes specified in Table 4-3. which meet local code requirements.
Time delay fuses or circuit breakers must be used to prevent nuisance trips.

Power requirements depend on the number and type of modules supplied for each system. For a system
with a single I/O chassis, size the input power source according to the rating of the MicroNet Plus power
supply to which the source is connected. Do not size the supply mains for the sum of the MicroNet Plus
power supply ratings when redundant supplies are used. MicroNet Plus supplies are redundant when
installed in the same chassis. Redundant supplies share the load between them equally, but each must
provide for full load in the event that one of the units is disabled. Table 4-3 gives the maximum overload
protection for supply mains connected to any single or redundant pair of MicroNet Plus main power
supplies. It is not recommended that both MicroNet Plus main power supplies of a redundant pair be
connected to a single source, since failure of that source would disable the system.
| Woodward 8444-1107 MFR300 kW Transducers with Protection |
| Woodward 8446-1062 easYgen-3400/3500, LS5 & RP-3000 MARINE Packages |
| Woodward 8444-1092 MFR300 kW Transducers with Protection |
| Woodward 8440-2056 easYgen-3100/3200 |
| Woodward 8440-2078 easYgen-3400/3500/P1/P2 |
| Woodward 8440-2079 easYgen-3400/3500/P1/P2 |
| Woodward 8444-1093 MFR300 kW Transducers with Protection |
| Woodward 8444-1109 MFR300 kW Transducers with Protection |
| Woodward 8440-2173 SPM-D2 Synchronizers |
| Woodward 8446-1048 easYgen-3400/3500, LS5 & RP-3000 MARINE Packages |
| Woodward 8440-1936 easYgen-3400/3500/P1/P2 |
| Woodward 8446-1046 easYgen-3400/3500, LS5 & RP-3000 MARINE Packages |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved