The EL3483 EtherCAT Terminal enables the monitoring of relevant electrical
data of the supply network. The voltage is measured internally via direct
connection of L1. L2. L3 and N. The internal measured values are compared
with threshold values preset by the user. The result is available as digital
information in the process image. The EL3483 checks for the correct phase
order L1. L2. L3. phase failure, undervoltage and overvoltage, and possible
phase asymmetry. An error bit is set in the case of an incorrect phase order
or the failure of a phase. Should, for example, an asymmetry or voltage error
occur, only a warning bit is set initially. In addition, an internally calculated
mains quality factor provides information about the quality of the monitored
voltage supply. The EL3483 offers basic functionality for mains monitoring
and analysis.

The EL3483 EtherCAT Terminal enables the monitoring of relevant
The EL3453-0100 EtherCAT power measurement terminal has voltage
inputs for up to 130 V AC for connecting voltage transducers, enabling
the monitoring of medium-voltage systems, for example.
The four current inputs are electrically isolated so that the terminal
can be used in all common grounded current transformer configurations
such as 2- or 3-transformer configurations with star or delta connection
incl. neutral conductor current measurement. The EL3453-0100 can be
used for simple grid analysis up to the 63rd harmonics analysis.
Alternatively, all readings can be combined in a power quality factor
for simplified diagnostics. Like all measured terminal data, the harmonic
content can be read via the process data. The EL3453-0100 offers the
“ExtendedRange” feature enabling the use of the full technical measuring
range, which equals 130% of the specified nominal measuring range.
In addition, the EL3453-0100 comes with the option of transmitting the
times of the last voltage and current zero crossing to thecontroller via
XFC technology. This can be used, for example, to carry out switching
operations to suit the application.
The EL3453 EtherCAT power measurement terminal has voltage
inputs for direct monitoring of high-capacity generators up to max.
690 V AC, as is common in the wind industry, for example.
No upstream voltage transformer is required. The four current
inputs are electrically isolated so that the terminal can be used
in all common grounded current transformer configurations such
as 2- or 3-transformer configurations with star or delta connectionz
incl. neutral conductor current measurement.
The EL3453 can be used for simple grid analysis up to the 63rd
harmonics analysis.
Alternatively, all readings can be combined in a power quality factor
for simplified diagnostics. Like all measured terminal data, the
harmonic content can be read via the process data.
The EL3453 offers the “ExtendedRange” feature enabling the use
of the full technical measuring range, which equals 130% of the
specified nominal measuring range.
In addition, the EL3453 comes with the option of transmitting the
times of the last voltage and current zero crossing to the controller
via XFC technology. This can be used, for example, to carry out
switching operations to suit the application.