Overview
PAC8000 Hybrid Control provides a fully integrated solution for process control,
logic automation and strategy development.
PAC8000 Hybrid Control provides a process engineer with the tools to design, implement, document,
and maintain a process control system using advanced control strategies.
PAC8000 Hybrid Control consists of a number of open system components.
The PAC8000 Hybrid Workbench is an integrated development environment that centralizes and coordinates project data including instrument indexes,
control strategies (process and logic) and project management.
It configures the control logic and generates an export database to create the operator (HMI) database.
A rugged field-mountable Control Platform, consisting of the PAC8000 Hybrid controller (8521- HC-MT) and the 8000 Process I/O system.
PAC8000 Controllers are used in conventional distributed control architectures,
with the I/O modules connected directly to the Controllers.
The same I/O modules may be used in remote IO architectures.
• 8 isolated, universal, input channels
• Configurable on a channel by channel basis: 4-20mA, THC, RTD, resistance &voltage
• 250V ac rms channel to channel isolation
• Thermocouple types B, E, J, K, N, R, S, T, W3. W5. Russian K, Russian L
• RTD Types Pt100. jPt100. Pt200. Pt500.Ni120. Cu10
• Volt input types ±120mV, 0-1V, 0-5V,1-5V, 0-10V, ±10V
• 2 or 3-wire RTDs
• 2 or 4-wire transmitters
• Non-incendive field circuits
• 24 V dc bussed field power required
CONFIGURABLE PARAMETERS
Sensor type
• User selectable
Alarms
• High-high, high, low and low-low
Alarm deadband (hysteresis)
• User defined value
Input dead zone
• User defined value
Channel status
• Active / inactive
Filter/sample rates
• User selectable
GENERAL SPECIFICATIONS
Common mode rejection (using 50/60Hz filter)
• > 120 dB @ 50/60 Hz
Series mode rejection (using 50/60Hz filter)
• > 65 dB @ 50/60 Hz
Maximum input voltage (except current I/P)
• ± 25V
Common mode voltage between channels
• 250 V ac rms
Isolation
• Channel to channel – 250 V ac rms
• Any channel to Railbus – 250 V ac rms
• Any channel to Bussed Field Power – 250 V ac rms
• Railbus to Bussed Field Power – 150 V ac rms
Input filter response
• Time constant 4 ms
Input impedance
• > 1 M ohm
Data Format
• 0 to 65535 corresponds to selected span
Features
PAC8000 I/O is a completely modular I/O solution for both general purpose and hazardous area applications.
It offers a wide variety of I/O functions, and has an open architecture that allows communication with
a variety of different field-buses by selecting the appropriate type of Bus Interface Module (BIM) or Controller.
Field terminals (one per I/O module) snap onto the carrier and accept field wiring without the need for additional terminals or connections.
They can be changed easily if damaged in the field. A comprehensive mechanical keying system ensures that equipment safety is maintained.
Carriers form PAC8000s physical and electrical backbone by providing a mounting onto a flat panel or T- or G-section DIN rail.
They support and interconnect the BIM or Controller, power supplies, I/O modules and field terminals,
and carry the address, data and power lines of the internal Railbus
Returns commoned internally
Pulse counting option
24 V dc bussed field power required
GE 8709-CA-08 I/O Carrier, 8 module with earth bar |
GE 8720-CA-04 4 module Intrinsically Safe carrier |
GE 8710-CA-04 4 module carrier |
GE 8723-CA-RB Railbus isolator carrier |
GE 8711-CA-NS Node services carrier, screw terminal LAN |
GE 8724-CA-PS Intrinsically Safe module power supply carrier |
GE 8712-CA-NS Node services carrier, Profibus-DP LAN |
GE 8725-CA-RB Railbus isolator carrier with PFM |
GE 8715-CA-BI BIM only carrier for Profibus & MODBUS LANs |
GE 8727-CA-08 8 module Intrinsically Safe carrier |
GE 8717-CA-PS Carrier for 8910-PS-DC |
GE 8729-CA-08 Intrinsically Safe Carrier, 8 module, 64-address system |
GE 8020-CE-RH R-HAND EXT. CARRIER |
GE 8044-CC-20 Carrier extension cable, 2.0m |
GE 8021-CE-LH Carrier extender, left hand |
GE 8080-FC-10 16-pin cable for 8618 (1m) |
GE 8030-CE-RH Intrinsically Safe Carrier extender, right hand |
GE 8081-FC-20 16-pin cable for 8618 (2m) |
GE 8031-CE-LH Intrinsically Safe Carrier extender, left hand |
GE 8082-FC-30 16-pin cable for 8618 (3m) |
GE 8034-CC-12 Intrinsically Safe Carrier Extension Cable set, 1.2m |
GE 8085-FC-10 20 + 24 pin cables for 8619 (1m) |
GE 8041-CC-35 Carrier extension cable, 0.35m |
GE 8086-FC-20 20 + 24 pin cables for 8619 (2m) |
GE 8042-CC-85 Carrier extension cable, 0.85m |
GE 8087-FC-30 20 + 24 pin cables for 8619 (3m) |
GE 8413-FK-DN 8913/4 PS DIN Rail Mounting Kit |
GE 8913-PS-AC 5A 12VDC & 5A 24VDC A/C Input P/S |
GE 8414-FK-SU 8913/4 PS Surface Mounting Kit |
GE 8914-PS-AC 10A 24VDC A/C Input P/S |