Memory Module Manufacturers ABB, Bailey Model(s)
ABB Bailey Infi 90, ABB Bailey Infi 90 and Net 90
Additional Information Used with IEPEP03/NPEP05 Power Entry Panels
Estimated Shipping Size Dimensions: 8.0" x 1.0" x 13.0" (20.3 cm x 2.5 cm x 33.0 cm)
Weight: 0 lbs 12.9 oz (0.4kg )
Memory Module
These accuracy settings are only used when negotiating for time mastership with
other nodes in the underlying Harmony control network.
Master Update Period
Master update period is the frequency that Harmony Server synchronizes time with
the underlying Harmony control network. This property is used only when Time
Synchronization is enabled. The permissible values are 120 to 3540 seconds.
Accuracy
Time synchronization accuracy of the Server is valid when the Server is in time
synchronization mode. The options are:
• Low accuracy (lowest accuracy); priority 0.
• Low accuracy battery backed; priority 3.
• High accuracy battery backed; priority 6.
• IIOIS20 node; priority 9.
• IIOIS20 SCSI; priority 10.
• PIMS SCSI; priority 11.
• Satellite clock system (highest accuracy); priority 12.
Message Wait Period
Message wait period is the Period that Harmony Server waits before attempting to
assume time mastership on the control network. This property is used only when
Time Synchronization is enabled. The permissible values are between 180 and 3660
seconds. Additionally, the configured value must greater than the Master Update Period.
Time Synchronization
Enable Time Synchronization
Determines whether or not the Server receives and sends the time synchronization
on the network. When enabled, the Server is in time synchronization with the
control network.