Part Number IS400JGPAG1A Manufacturer General Electric Country of Manufacture
As Per GE Manufacturing Policy Series Mark VI/VIe Function Module Availability
IS400JGPAG1A is a Ground Terminal Board and it's a part of GE Speedtronic Mark VIe gas turbine control.
The ground and power board (JGPA) is a long narrow board that mounts adjacent to
PCAA where shield wires are terminated. JGPA provides shield wire
terminal points that may be tied directly to the underlying functional earth sheet metal or
wired to a preferred grounding point.
In this respect, it is very similar to the JGND board offered as an option with other Mark VIe terminal boards.

If a module had been previously configured with Logicmaster 90-30/20/Micro software and the
number of actively scanned channels has been changed from 16, that number will be displayed
on the bottom line of the Hand-Held Programmer display following the AI. You can edit data
with the Hand-Held Programmer only for the active channels, but can not change the number of
actively scanned channels.
The maximum number of 16-Channel Analog Current Input modules which may be installed in a
system are:
4 in a Model 311, Model 313, and Model 323 system
8 in a Model 331 system
12 in a Model 340 and Model 341 system
51 in a Model 351 and Model 352 system
When planning the module configuration for your application you must also consider the load
capacity of the installed power supply and the total load requirements of all modules that are
installed in the baseplate. TEL:+8618144100983
Refer to the Series 90-30 Programmable Controller Installation Manual, GFK-0356 for details on
power supplies and module load requirements.
The bottom LED, User Supply OK, indicates that the user provided 24V supply is within
specifications, thereby enabling the analog side of the module to work properly
This exceptional control solution is compact, cost-effective, and adaptable, serving as a compact PLC, distributed
I/O, or distributed control system.
The 16-Channel Analog Current Input module provides up to 16 single-ended input channels,
each capable of converting an analog input signal to a digital value for use as required by your application.
References Used
The number of 16-Channel Analog Current Input modules which may be installed in a system
depends on the amount of %AI and %I references available. Each module uses 1 to 16 %AI
references (depending on the number of channels enabled) and from 8 to 40 %I (depending on
alarm status configuration) references.