Refer to the Series 90-30 Programmable Controller Installation Manual, GFK-0356 for details on
power supplies and module load requirements.
The bottom LED, User Supply OK, indicates that the user provided 24V supply is within
specifications, thereby enabling the analog side of the module to work properly
This exceptional control solution is compact, cost-effective, and adaptable, serving as a compact PLC, distributed
I/O, or distributed control system.
The 16-Channel Analog Current Input module provides up to 16 single-ended input channels,
each capable of converting an analog input signal to a digital value for use as required by your application.
References Used
The number of 16-Channel Analog Current Input modules which may be installed in a system
depends on the amount of %AI and %I references available. Each module uses 1 to 16 %AI
references (depending on the number of channels enabled) and from 8 to 40 %I (depending on
alarm status configuration) references.
Configuring IC693ALG223 Using Hand-Held Programmer
You can also configure the 16-Channel Analog Current Input module using the Series 90-30
Hand-Held Programmer. In addition to the information in this section, refer to GFK-0402, the
Hand-Held Programmer for Series 90-30/20/Micro Programmable Controllers User’s Manual
for more information on configuration of Intelligent I/O modules.
Although you can change the number of actively scanned channels with the Logicmaster
90-30/20/Micro configurator function, the Hand-Held Programmer does not support editing the
number of actively scanned channels. If the 16-Channel Analog Input module is initialized by
a Hand-Held Programmer, the number of actively scanned channels is 16.