Application and features
Application
The protective stator earth fault relay type RMC-142D forms part of a complete
DEIF series of relays for protection and control of generators. The RMC-142D
is primarily designed for land-based installations. Also available are short circuit
relays (RMC-111D), combined short circuit and over-current relays (RMC-122D)
and double over-current relays (RMC-132D).
The RMC-142D is CE-marked and is applied for protection of voltage sources and
load networks against earth fault in a solid earthing or a low-resistance earthing system.

Measuring principle
The relay measures the leakage or a short circuit from one or more of the phases to earth.
In order to obtain a short response time on a fault condition, the measurement is based
on peak values.
The earth fault current protection is for example obtained by connecting an external current
transformer in the star point of the protected voltage source.
In order to prevent malfunction due to 3rd harmonic, the RMC-142D is equipped with
a special filter cutting off frequencies higher than 50/60 Hz.
The set point values are set on the front of the relay by means of potentiometers.
If exceeded, a fault signal is generated, and the associated yellow LED is lit.
Timer functions
When the set point is exceeded, its timer starts and will run as long as the fault condition prevails.
If the fault disappears, the timer is reset. When the timer expires, the contact is activated
and the associated red LED is lit.
Relay outputs
The RMC-142D is provided with two outputs with maximum contacts either normally
energised or normally de-energised.
The contact may be set to open or close on activation.
Normally energised contact
Recommended for warning and alarm purposes.
In case of an auxiliary supply dropout, the contact is immediately activated.
Normally de-energised contact
Recommended for installations for regulating and control purposes.
An auxiliary supply failure will not result in an unwanted activation of the contact.
Latch circuit
The contact can be locked in its warning position, even if the earth faulty current
(leakage current) returns to normal (add "L" to contact type in order specifications,
if this is required). The latch circuit is reset by disconnecting the auxiliary supply.
Hysteresis
In order to avoid "chatter" on the relay contacts the contact functions are provided
with a hysteresis, that is a difference of 2 % of full scale between energising and
de-energising of the delay.
Power-up/power-down circuits
The RMC-142D is provided with a 200 ms power-up circuit, ensuring the correct function
of the relay on connection of the auxiliary voltage.