Product Description
The Serial Interface consists of a serial card and a terminal
block. The card contains two serial communications
ports that support RS232 and RS422/485 half duplex, or
RS422/485 full duplex signals. These ports are individually
configurable and support data rates from 300 Baud up to
115 KBaud.
The S-series card plugs into an 8-wide I/O carriers in any of
the possible 64 slots and communicates with the S-series
controllers. LEDs, located on the front of the card, show the
power, error, and port status of the interface at a glance.
The standard Modbus protocol includes the Serial Interface,
the Modbus RTU, and ASCII communications protocol
as defined in the Modicon Modbus Protocol Reference
Manual dated March 1992 (PI-MBUS-300 REV D). Each Serial
Interface port may be configured as either a master or
slave device.
The serial card supports the following features using the
Modbus protocol:
• Reading input data from Modbus coils, input status,
holding registers and normal input registers.
• Writing output data to coils and holding registers.
• Output data can be written in single coil, register mode,
or complete data set mode. This output mode is a
configurable parameter.
• Input data can be read in as a complete data set,
providing the best performance.
The serial card supports the input and/or output of
16 different data sets per serial port, for a total of 32 data sets
per Serial Interface.
Serial dataset registers can be referenced directly in control
modules as analog or discrete I/O providing fast easy data
exchange with the serial device. Direct module-to-Dataset/
register references are recommended for control signals.
Alternatively, users can read multiple registers form a
Dataset into a single “marshalling” module at the cost of
a single DST. Marshalling modules provide a cost effective
way to integrate serial data from analyzers and other data
sources. Serial dataset registers can also be passed as
SCADA values directly to Workstations and Continuous
Historians without consuming DST’s.
Both Modbus RTU and Modbus ASCII communications
modes are supported by standard Modbus protocol.