Analog inputs
• Three phase currents: 5/1 A programmable
• Ground current: 5/1 A programmable or 0.2 A
Rated frequency: 60/50 Hz programmable
• Three-phase and ground voltages: programmable
nominal secondary voltage (available as options)
Binary inputs and outputs
• Four, eight with VT inputs, binary inputs standard
• Two NO outputs with trip circuit monitoring
• Three NO outputs
• One Form C output and self-check alarm output
• Additional binary inputs and outputs available as options
Communication
• IEC 61850-8-1 with GOOSE messaging
• DNP3.0 Level 2+ over TCP/IP
• Modbus over TCP/IP
• Time synchronization via SNTP (primary and backup servers)
• Optional serial RS-485 port programmable for
DNP3.0 Level 2+ or Modbus RTU
• Optional IRIG-B time synchronization
• Optional HSR/PRP communication
• Optional IEEE1588v2 time synchronization (available
with REF615 V5.0 and later)
• IEC61850-9-2LE (available with REF615 V5.0 and later)
Product dimensions and weights
• Frame: 6.97” (177 mm) W x 6.97” (177 mm) H
• Case: 6.57” (165 mm) W x 6.30” (160 mm) H x 6.10”
(155 mm)
• Weight: Relay - 7.72 lbs. (3.5 kg); Draw-out unit - 3.97
lbs. (1.8 kg)
Tools
• PCM600 V2.8 for setting, configuration and data retrieval
• COM600 Station Automation series products V5.0
• Web browser based user interface (IE 11 or later)
Certificates
• UL Listed product, File E103204
Control voltage
• Option 1: 48 ... 250 V dc, 100 … 240 V ac
• Option 2: 24 ... 60 V dc