Standardized communication
REF615 supports the new IEC 61850 standard for in
ter-device communication in substations. The relay
also supports the industry standard DNP3.0 and Mod
bus® protocols. The implementation of the IEC 61850
substation communication standard in REF615 en
compasses both vertical and horizontal communica
tion, including GOOSE messaging and parameter set
ting according to IEC 61850-8-1. The substation
configuration language enables the use of engi
neering tools for automated configuration, com
missioning, and maintenance of substation devices.
Pre-emptive condition monitoring
For continuous knowledge of the operational avail
ability of the REF615 features, a comprehensive set
of monitoring functions to supervise the relay
health, the trip circuit, and the circuit breaker
health is included. The breaker monitoring can in
clude checking the wear and tear of the circuit
breaker, the spring charging time of the breaker
operating mechanism and the gas pressure of the
breaker chambers. The relay also monitors the
breaker travel time and the number of circuit
breaker operations to provide basic information
for scheduling breaker maintenance.
Bus protection via GOOSE
The IEC 61850 implementation in REF615 also in
cludes fast peer-to-peer communication, over the
substation bus. Use GOOSE communication be
tween REF615 IEDs of the incoming and outgoing
feeders of a substation cooperate to form a stable,
reliable, and high-speed busbar protection system.
The cost-effective GOOSE-based busbar protec
tion is obtained by configuring the IEDs and the
operational availability of the protection is assured
by continuous supervision of the protection IEDs
and their GOOSE messaging over the station bus.
No separate hard-wiring is needed for the horizon
tal communication between the switchgear cubicles.