Adapts M‑2001 Series Digital Tapchanger Control to Replace Pennsylvania
Transformer and McGraw‑Edison 110. 220. 220A, 550 and 550B
Type LTC Transformer Controls Produced Before 1963
• Connects easily to the M‑2001 Series Digital Tapchanger Control using
mounting screws and 24‑pin connector
• Provides direct mechanical replacement of the existing LTC transformer
control using the same two knurled knobs from the existing control
• Provides built‑in CT shorting protection when the M‑2001 Series Digital
Tapchanger Control is removed.

The M‑2379 is an adapter panel which, when combined with the M‑2001
Series Digital Tapchanger Control, provides convenient direct replacement
for the following Pennsylvania Transformer and McGraw‑Edison LTC
transformer controls manufactured before 1963: 110. 220. 220A, 550 and
550B.
Interface
External connections are made at two terminal blocks located on the rear
panel of the M‑2379B and two terminal blocks located on the printed circuit
board. These terminal blocks provide access to auxiliary functions, including
self-test alarm, user-programmable alarm, auto disable and manual raise/
lower. A fifth terminal block provides for the addition of the M‑0329B LTC
Backup Control. The two knurled knobs must be saved from the existing
control cabinet.
Features
Separate fuses for test terminal, voltage sensing and motor power are on
the front panel. Spare fuses for each are in the fuse holder. Binding posts on
the front panel allow easy connections for test procedures.
RAISE/OFF/LOWER, AUTO/OFF/MANUAL and VOLTAGE SOURCE switches,
DRAG HANDS RESET button, and NEUTRAL LIGHT are standard 90 BACK UP
ALARM will light to indicate that the optional M‑0329B LTC Backup Control is
blocking any M‑2379B commands. MOTOR POWER button allows resetting
of the motor power circuit VOLTAGE BREAKER button allows resetting of the
voltage circuit breaker. HEATER SWITCH turns the heater on and off
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms to
chassis or instrument ground for one minute with a leakage current not to
exceed 25 mA, for all terminals to ground. Input and output circuits are
electrically isolated from each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected
against system transients. Units pass all requirements of ANSI/IEEE
C.37.90.1-1989 defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers.
Environmental
Temperature Range: Functionality is maintained from ‑40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non‑condensing).
Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.
Physical
Size: 22" high x 17" wide x 4‑3/8" deep (55.9 cm x 43.2 cm x 11.1 cm)
Approximate Weight: 6 lbs, 8 oz (3.0 kg)
Approximate Shipping Weight: 9 lbs, 8 oz (4.3 kg)
Approximate Weight with M‑0329B Option: 10 lbs, 8 oz (4.8 kg)
Approximate Weight with M‑2001 Series Digital Tapchanger Control: 10 lbs, 3 oz (4.6 kg)
Approximate Shipping Weight with M‑0329B Option: 13 lbs, 8 oz (6.1 kg)
Warranty
The M-2379 Adapter Panel is covered by a five year warranty from date of shipment.
Specification subject to change without notice.