Adapts M‑2001 Series Digital Tapchanger Control to Replace McGraw‑Edison
550 BHS LTC Transformer Controls
• Connects easily to the M‑2001 Series Digital Tapchanger Control using
mounting screws and 24‑pin connector
• Provides direct mechanical replacement of the existing control using the
same two hinge pins
• Provides built‑in CT shorting protection when the M‑2001 Series Digital

Tapchanger Control is removed
The M‑2354C is an adapter panel which, when combined with the M‑2001
Series Digital Tapchanger Control, provides convenient direct replacement
of McGraw‑Edison 550 BHS LTC transformer controls. The M‑2354C consists
of a front panel, and mounts into the control cabinet. The hinge hardware,
knob, and the mounting hardware must be saved from the original control.
Interface
External connections are made via a wiring harness that connects from a
fifteen‑position terminal block to the two terminal blocks on the existing
control cabinet. An additional terminal block provides access to aux iliary
functions, including self‑test alarm, user‑programmable alarm, auto disable
and manual raise/lower. An auxiliary current transformer is supplied to
convert the 5 A load current into the 0.2 A used by the control.
Features
Separate fuses for test terminal, voltage sensing and motor power are on
the front panel. Spare fuses for each are in the fuse holder.
Binding posts on the front panel allow easy connections for test procedures.
RAISE/OFF/LOWER, AUTO/OFF/MANUAL and VOLTAGE SOURCE switches,
DRAG HANDS RESET button, and NEUTRAL LIGHT are standard.
NEUTRAL LIGHT will light to indicate that the regulator or transformer is
in the neutral position, for those products equipped with a circuit for this
purpose.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms to
chassis or instrument ground for one minute with a leakage current not to
exceed 25 mA, for all terminals to ground. Input and output circuits
are electrically isolated from each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected against
system transients. Units pass all requirements of ANSI/IEEE C.37.90.1‑1989
defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers.
Environmental
Temperature Range: Functionality is maintained from ‑40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non‑condensing).
Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.