Adapts M‑2001 Series Digital Tapchanger Control as a Replacement
for General Electric Static LTC Transformer and Regulator Controls
and some Balance Beam Models
• Connects easily to the M‑2001 Series Digital Tapchanger Control
using mounting screws and 24‑pin connector
• Provides direct mechanical replacement of the existing control
• Provides built‑in CT shorting protection when the M‑2001 Series
Digital Tapchanger Control is removed
• Optional SCADA Cutout (Local/Remote) switch (for use with SCADA
enabled M‑2001C controls) allows Local Blocking of SCADA commands
• Optional SCAMP™ (SCADA Controllable Auto/Manual Pushbutton)
switch replaced AUTO/OFF/MANUAL toggle switch
• Optional 2 Level Local Voltage Reduction Switch

The M‑2280B is an adapter panel which, when combined with the
M‑2001 Series Digital Tapchanger Control, provides convenient direct
replacement for General Electric static LTC transformer and regulator
controls and some balance beam models.
Interface
External connections are made to a terminal block located on the top
of the rear panel of the M‑2280B.
Additional connections may be made to two terminal blocks located on
the printed circuit board of the adapter panel. These terminal blocks
provide access to auxiliary functions, including self‑test alarm, user
programmable alarm, auto disable and manual raise/lower.
Features
Separate fuses for test terminal, voltage sensing and motor power are
located on the front panel. Spare fuses for each are in the fuse holder.
Binding posts on the front panel allow easy connections for test procedures.
RAISE/OFF/LOWER, AUTO/OFF/MANUAL and VOLTAGE SOURCE switches,
DRAG HANDS RESET button, and NEUTRAL LIGHT are standard.
NEUTRAL LIGHT will light to indicate that the regulator is in the neutral
position, for those products equipped with a circuit for this purpose.
Options
SCADA CUTOUT switch allows Local blocking of SCADA commands (for
use with SCADA enabled M‑2001C controls). The SCADA Cutout switch
must be used with a M-2001 Series Control with firmware version
D‑0146V08.01.22 or later installed.
SCAMPTM (AUTO/MANUAL) pushbutton switch allows the Auto/Manual
state on the adapter panel to be changed by a SCADA command.
The SCAMP pushbutton switch must be used with a M‑2001 Series Control
with firmware version D-0146V08.05.XX or later installed.
Voltage Reduction switch allows 2 levels of Voltage Reduction to be selected.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms
to chassis or instrument ground for one minute with a leakage current not
to exceed 25 mA, for all terminals to ground. Input and output circuits
are electrically isolated from each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected against
system transients. Units pass all requirements of ANSI/IEEE C.37.90.1-1989
defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected
against electromagnetic radiated interference from portable communications
transceivers.
Environmental
Temperature Range: Functionality is maintained from -40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non-condensing).
Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.