Adapts M‑2001 Series Tapchanger Control to Replace:
• Siemens (Allis‑Chalmers)
• TSEA Toshiba Regulator Controls
Directly replaces Siemens
(Allis‑Chalmers) models:
MJ‑1A, MJ‑2A, MJ‑3. MJ‑3A, MJ‑X;
IJ‑2. IJ‑2A; SJ‑4. SJ‑5. SJ‑6; UJ‑2.
UJ‑4. UJ‑5. UJ‑5C, some UA Series
• Provides direct mechanical replacement of a Siemens regulator control
using the existing quick disconnect terminal block
• Provides built-in CT shorting protection when the M-2001 Series Digital
Tapchanger Control is removed

• Optional SCADA Cutout switch allows local blocking of SCADA commands
(for use with SCADA enabled M-2001C controls)
• Optional SCAMPTM (SCADA Controlled Auto/Manual Pushbutton) replaces
AUTO/OFF/MANUAL toggle switch and allows the Auto/Manual state of
the adapter panel to be changed by a SCADA command
• Optional Voltage Reduction switch allows Local Voltage Reduction
1 or 2 to be initiated
• Siemens optional 10 position male PDS Connector Half available
M-2271B Adapter Panel – Specification
The M‑2271B is an adapter panel which, when combined with the M‑2001
Series Digital Tapchanger Control, provides convenient direct replacement
for Siemens (Siemens‑Allis and Allis‑Chalmers) and TSEA Toshiba regulator
controls.
Interface
External connections are made via a wiring harness that connects from a
sixteen‑position terminal block to the existing quick disconnect terminal block
on the Siemens control cabinet, or the existing terminal block on the TSEA
Toshiba control cabinet. The Siemens harness may be ordered with the optional
10 position male pin PDS Connector Half.
An additional terminal block provides access to auxiliary functions, including
self‑test alarm, user programmable alarm, auto disable and manual raise/lower.
Features
Separate fuses for test terminal, voltage sensing and motor power are on the
front panel. Spare fuses for each are in the fuse holder.
Binding posts on the front panel allow easy connections for test procedures.
RAISE/OFF/LOWER, AUTO/OFF/MANUAL and VOLTAGE SOURCE switches,
DRAG HANDS RESET button, and NEUTRAL LIGHT are standard. AUTO/OFF/
MANUAL switch may be configured for Switch Status detection.
NEUTRAL LIGHT will light to indicate that the regulator is in the neutral position,
for those regulators equipped with a circuit for this purpose.
Available Options
SCADA Cutout switch allows the local blocking of SCADA commands (for use
with SCADA enabled M-2001C controls). Use of the SCADA Cutout switch
requires a M-2001C Control with firmware version D‑0146V08.01.22 or later
installed.
SCAMP™ (SCADA Controlled AUTO/MANUAL Pushbutton) switch allows the
Auto/Manual state on the adapter panel to be changed by a SCADA command.
Use of the SCAMP pushbutton switch requires a M-2001C Control with firmware
version D-0146V08.06.XX or later installed.
Voltage Reduction (VR1/OFF/VR2) switch allows Local Voltage Reduction 1 or 2
to be initiated.
Siemens PDS Connector: 10 position Male Pin Connector Half, #421‑00251.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms to chassis
or instrument ground for one minute with a leakage current not to exceed 25 mA,
for all terminals to ground. Input and output circuits are electrically isolated from
each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected against system
transients. Units pass all requirements of ANSI/IEEE C.37.90.1-1989 defining surge
withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers.
Environmental
Temperature Range: Functionality is maintained from ‑40° to +85° C.
Humidity: Functionality is maintained under 95% relative humidity (non‑condensing).
Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth.