• Designed to interface with the M-7679 R-PAC.
• Allows the M-7679 R-PAC to monitor third party external power supplies and
12/24 V battery chargers.
• Provides four 0-30 Vdc Analog inputs. Using S-7600 IPScom communications
software, these inputs can be monitored and configured with two level
alarm settings per channel, and used in IPSlogic custom configurations.
• Monitor and test the battery system. Turns off the battery supply to enter
sleep mode during power loss.
• Transient and reverse polarity protected
• Operates on DC power from 8 to 30 V
• Substation hardened -40° C to +85° C
• Conformal coated

Introduction
The M‑2035 Interface Module monitors power supplies and battery chargers
used in Reclosers that have been retrofitted to operate with Beckwith
Electric's M-7679 R-PAC system. This analog to digital interface measures
voltage, current, and current direction which can be monitored with the
same S-7600 IPScom communication software used with the recloser control.
The interface module can be DIN rail mounted during installation of the
M-7679 R-PAC and includes a SATA cable for easy hookup to the Aux I/O port
in the recloser control. The module will accept 8 to 30 Vdc power from the
existing power supply and batteries.
The module features essential indicator lights for battery and communication
status plus on‑board and remote manual wake-up pushbuttons to restore
function after a power failure. Four extra analog to digital inputs are available
for voltage measurements up to 30 Vdc. The module is able to periodically
test the batteries by briefly disconnecting the charger with a high side switch
and switching on a resistive load for five seconds.
Configurable DC Power Monitoring
Four analog inputs allow the user to remotely monitor DC voltages from 0 to
30 Vdc. Each input can be configured with two setpoints to report when voltage
drops below the specified levels. The analog to digital converter is 12 bit and
averaging is done over 128 samples to increase resolution to 16 bits.
Analog metering data is updated every 64 ms.
Summary of Operation
• Installed between the battery and battery charger (with fuse protection for
reverse polarity of charger or battery), the M-2035 measures battery voltage,
charge and discharge current, detects AC power loss, and sends the
measurements to the controller through the SATA communication interface.
• Continuously monitors charger voltage. Conducts scheduled battery load
tests on 12 and 24 V battery configurations while automatically disconnecting
and reconnecting the battery charger.
• During tests, module controls the battery load resistor via command from
the M-7679 R-PAC so that when the load resistor is turned on, it disconnects
the high side switch. Reconnects high side switch after load resistor is turned
off. Does not turn on load resistor if loss of main power is detected.
• When running on battery power, the M-7679 R-PAC commands the M-2035
module to enter low power mode if the battery voltage drops below "Vmin Bat"
setting, disconnecting the M-7679. Local or remote pushbutton provides "
wakeup from sleep" functionality. When pressed, the pushbutton releases
module from sleep and activates high side switch to reconnect the battery
and power supply.
• While in the sleep mode, the M-2035 module wakes up every 5 seconds to
measure voltage at Charger Input (TB4) to determine when main power
returns. Provides "wakeup" functionality when main power is restored.
Turn-on/off Battery Load Test Command
Test frequency is user defined in the Battery Charger common setpoints in
IPScom communication software.
The M-7679 R-PAC issues the "Turn-on/off Battery Load Test" command to the
M-2035 to test the battery capacity only when the charger is operating from
the main power supply.
Battery Supply Off Command
When the battery voltage decreases to less than "Vmin Batt" (Figure 1) the
battery supply to the M-7679 R-PAC will be turned off to protect the battery.
The M-2035 remains connected to the battery. Discharging batteries below
certain levels will shorten the life of or damage the battery.
Threshold voltages can be edited in IPScom/Common Setpoints/IED Power
Supply/Battery Charger Monitor screen.
Wakeup System Command
The Wakeup system command is initiated with local panel pushbutton, allowing
the user to wake module from the Sleep Mode that was initiated by the Battery
Supply Off command. The wakeup system command restores power to the unit
for a user defined time period. If the main source power has not been restored,
the Battery Supply Off command will be repeated. The loss of main power is
determined by monitoring the battery current throughput polarity.
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2026 Cld , All Rights Reserved K-JIANG All rights reserved