• Available in four different Mounting configurations shown above, plus
Surface Mount (Option S1)
• Facilitates standardization for small/medium intertie and generator
protection applications
• Microprocessor-based relay provides 15 protective relay functions,
including Sync-Check, 2 programmable outputs and 2 programmable
inputs
• Relay voltage inputs can be directly connected (no VT required) for
voltages 480 V or less
• Local and remote serial communications (MODBUS protocol)
capability for monitoring and control functions

Protective Functions
• Sync-check with Phase Angle, ∆V and ∆F with dead line/dead bus
options (25)
• Phase undervoltage (27) protection
• Ground undervoltage (27G) protection
• Dual-setpoint, single or three phase, directional power detection that
can be selected as over/ under power protection (32)
• Dual-zone, offset-mho loss-of-field for generator protection (40)
• Sensitive negative sequence overcurrent protection and alarm (46)
• Negative sequence overvoltage (47)
• Inverse time residual overcurrent (51N)
• Phase overcurrent with voltage restraint/control (51V) protection
• Phase overvoltage (59) protection
• Ground overvoltage (59G) protection
• Peak overvoltage (59I) protection
• VT fuse-loss detection and blocking (60FL)
• Reconnect enable for intertie protection (79)
• Four-step over/under frequency (81) protection
Standard Features
• 2 programmable outputs, 2 programmable inputs, and 1 self-test output
• Oscillographic recording (COMTRADE file format)
• Time-stamped sequence of events recording for 32 events
• Metering of Voltage, Current, real and reactive Power, Power Factor,
Frequency, and Positive Sequence Impedance
• One RS-232 port (COM1) on front and one RS-232 or 485 port (COM2)
on rear
• M-3810A IPScom for Windows Communications Software
• MODBUS protocol
• Supports both 50 and 60 Hz applications
• Accepts 1 A or 5 A rated CT inputs
• Relay voltage inputs can be directly connected (no VT required) for
voltages ≤ 480 Vac
• Continuous Self-Diagnostics
Description
M‑3410A Intertie/Generator Protection Relay – Specification
The M-3410A Intertie/Generator Protection Relay is intended for the
protection of the intertie between the utility and dispersed generation.
It is also suitable for the protection of synchronous and induction
generators.
Communications and control features of the M-3410A are accomplished
utilizing the M-3810A IPScom for Windows Communications Software.
Oscillographic Recorder
The oscillographic recorder provides comprehensive data recording of all
monitored waveforms, input contacts, and output contacts, storing up to
120 cycles of data. The total record length is configured for one or two
partitions. A programmable post trigger delay (5 to 95%) is incorporated
to capture breaker operation.
The oscillograph is triggered remotely using the serial interface, designated
status input signals, or M-3410A programmable output operations.
Storage of oscillographic records is nonvolatile and will be retained even
without power, as long as the on-board battery is healthy.
Oscillographic data can be downloaded using serial communication in
Common Format For Transient Data Exchange (COMTRADE) format as
specified by IEEE Standard C37.111-1999.
Sequence of Events
A total of 32 nonvolatile events can be stored. The recorded information
includes the function(s) operated, the function(s) picked up, input/output
contact status and time stamp. The events can be retrieved through the
communications port. After the 32nd event is stored, additional events
result in the oldest event being dropped (FIFO).
The information is time-stamped to 1 ms resolution.