Power Engineering 
K-JIANG
NameDescriptionContent
Current Location:

Emerson Ethernet I/O Card (EIOC) Supported Industrial Ethernet Protocols

From:Emerson | author:Mr.Chen | Time :2024-12-18 | 1704 view: | 🔊 Click to read aloud ❚❚ | Share:

Supported Industrial

Ethernet Protocols:

Modbus TCP Interface

The Modbus TCP interface will support Modbus data

sources such as PLCs, MCCs, analyzers and similar devices

communicating Modbus TCP. The Modbus TCP interface is a

Modbus Client reading and writing data from/to Modbus Server

devices. The Modbus server devices can be Modbus TCP devices

or Modbus serial devices using a Modbus TCP gateway.

The Modbus TCP interface supports the following types of

data access:

„ Reading input data from Modbus Coils, Discrete Input,

Holding Registers, and Input Registers.

„ Writing output data to Coils and Holding registers.

All reads will be performed periodically and outputs will be

sent when they are written.

EtherNet /IP

The EtherNet/IP protocol allows data sources such as

PLCs, Intelligent Field Devices (IFDs), variable-speed drives,

MCCs, and analyzers; as well as other devices communicating

EtherNet/IP to connect directly in to DeltaV via the EIOC.

The EtherNet/IP interface will support connections for

both implicit and explicit messaging to allow access to both

Class 1 and Class 3 EtherNet/IP I/O adapters. Redundancy with

EtherNet/IP Class 1 Implicit and Class 3 Explicit messaging

for control (sending outputs to the devices) require special

considerations due to exclusive owner communications defined

by the protocol. Please refer to the DeltaV System Planning

Guide for more information. Class 3 PCCC and UCMM with

Logix tags message classes are also supported.

IEC 61850 (MMS)

The IEC 61850 MMS interface will allow data from Intelligent

Electronic Devices (IEDs) such as motor protection relays,

motor starters, motor control centers, switchgear, and similar

MMS-based devices to be integrated into DeltaV. The MMS

interface will be a client reading and writing data from/to the

Intelligent Electronic Device which acts as the server.

The EIOC only supports reading and writing of real time

signals using this protocol. Reading historical data or

Goose applications are not supported.

OPC UA Client

The OPC UA Client in the EIOC provides native client

implementation of a Data Access profile (real time data)

compliant with OPC UA version 1.03. The OPC UA client will

read and write up to 30,000 real time signals coming from

up to 64 OPC UA servers.

EtherNet/IP Control Tag Integration protocol

The EtherNet/IP Control Tag Integration protocol utilizes

EtherNet/IP Class 3 messaging to provide integration with

tag-based PLC data sources. Referencing data by tag name

eliminates the need for register mapping. Read or write up

to 10 signals per tag, and up to 2000 tags per EIOC for a total

of 20,000 signals. The EtherNet/IP Control Tag Integration

protocol supports reading string type signals and read/write

of arrays up to 64 elements each (max 100 arrays per EIOC).

The EtherNet/IP Control Tag Integration protocol supports

integration with ControlLogix and CompactLogix PLCs

utilizing tags.

Parallel Redundant Protocol (PRP)

PRP is a network protocol standard for Ethernet that provides

seamless failover against failure of any network component.

Therefore, it is a great solution when high availability and short

switchover time is required (e.g. electrical monitoring using

IEC 61850 MMS). PRP allows for communications in Primary and

Secondary ports of the Ethernet Device Network in the EIOC to

happen at the same time. This means that a device connected

to the Ethernet Device network is getting the same information

at the same time, through different network paths. In case of

failure in one of the networks it basically provides a zero-time

to recovery (no time to switchover) and eliminates any single

point of failure in a redundant Ethernet Device Network.

PRP is independent of the application-protocol and can be

used by most Industrial Ethernet protocols. In the EIOC,

PRP is an optional feature than can be enabled at the port level

and is available with all the protocols supported in the EIOC.

When enabled, PRP runs on top of the protocol that is selected

at that time.

For PRP to work properly, the Ethernet Devices connected to

the redundant network needs to support PRP natively as well.

If the devices do not support PRP natively, then a RedBox must

  • GE Multilin 750-P5-G5-S5-HI-A20-G 750 Management Relay
  • GE Multilin 750-P5-G5-D5-HI-A20-R 750/760 Feeder Mgmt Relay Series
  • GE Multilin 750-P5-G5-D5-HI-A20-G Management Relay
  • GE Multilin 750-P5-G1-D5-HI-A20-R Multilin 1A Zero Sequence Current Inputs
  • GE Multilin 750-P1-G1-S1-HI-A20-R-T-H Feeder Management Relays
  • GE Multilin 750-P1-G1-S1-HI-A20-R Feeder Management Relays
  • GE Multilin 750-P1-G1-D1-HI-A20-R Base Unit 750 Relay
  • GE Multilin 239-RTD-AN-H motor protection relay
  • GE Multilin 489-P5-HI-A20-T-H Generator Management Relay for 489 Series
  • GE Multilin 489-P5-HI-A20-T Generator Management Relay for 489 Series
  • GE Multilin 489-P5-HI-A20-E-H Relay Motor Management
  • GE Multilin 489-P1-LO-A20 489 Motor Management Relay Base Unit
  • GE Multilin SR469-P5-LO-A20-T Motor Management Relay
  • GE Relay from GE Grid Solutions SR469-P5-LO-A20-E
  • GE Multilin SR469-P5-LO-A20 Motor Management Relay with Case
  • GE Multilin SR469-P5-HI-A20-T 469 Series Relay
  • GE Multilin SR469-P1-HI-A1-E-H 469 Series Relay
  • GE Multilin SR469-P1-H1-A1-E 469 Series Relay
  • GE Multilin 469-P5-LO-A20-T Phase Current Input 5 A Phase CT Secondaries
  • GE Multilin 469-P5-LO-A20-E LO Control Power with 4-20mA Analog Outputs
  • GE Multilin 469-P5-LO-A20 Motor Management Relay
  • GE Multilin 469-P5-HI-A20-E-H Motor Management Relay
  • GE Multilin 469-P5-HI-A20 469 Motor Management Relay
  • GE Multilin 469-P1-HI-A1-E-H 469 Base Unit Motor Management Relay
  • GE Multilin 469-P1-H1-A1-E 469 Motor Mgmt Relay
  • Beckhoff ED2504 | EtherCAT Terminal, 4-channel PWM output
  • Beckhoff EL2262 | EtherCAT Terminal, 2-channel digital output
  • Beckhoff EL2258 | EtherCAT Terminal, 8-channel digital output
  • Beckhoff EL2252 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 0.5 A, timestamp
  • Beckhoff EL2212 | EtherCAT Terminal, 2-channel digital output
  • Beckhoff EL2202-0100 | EtherCAT Terminal, 2-channel digital output
  • Beckhoff EL2202 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 0.5 A, push-pull, tristate
  • Beckhoff EL2124 | EtherCAT Terminal, 4-channel digital output, 5 V DC, 20 mA
  • Beckhoff EL2088 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A, ground switching
  • Beckhoff EL2084 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, ground switching
  • Beckhoff EL2068 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A, with channel diagnostics
  • Beckhoff EL2044 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A, with extended diagnostics
  • Beckhoff EL2042 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 2 x 4 A/1 x 8 A
  • Beckhoff ED2034 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A, push-in, with channel diagnostics
  • Beckhoff EL2034 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A, with diagnostics
  • Beckhoff ED2032 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 2 A, push-in, with channel diagnostics
  • Beckhoff EL2032 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 2 A, with diagnostics
  • Beckhoff EL2024-0010 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A
  • Beckhoff EL2024 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A
  • Beckhoff EL2022 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 2 A
  • Beckhoff EL2014 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, with extended diagnostics
  • Beckhoff ELX2008 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 30 mA, Ex i
  • Beckhoff ED2008 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A, push-in
  • Beckhoff EL2008 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A
  • Beckhoff EL2004 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A
  • Beckhoff ELX2002 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 45 mA, Ex i
  • Beckhoff EL2002 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 0.5 A
  • TMEIC TM21-TG Series 2-Pole Generator
  • TMEIC TM21-TG Series 4-Pole Generator for Turbine Drive
  • TMEIC Air-Cooled Type Synchronous Generators
  • TMEIC TMdrive-XL85 Medium Voltage AC Drives
  • TMEIC TMdrive-30 Medium Voltage AC Drives
  • TMEIC TMdrive-MVG2 Medium Voltage AC Drives
  • TMEIC TMdrive-70 Medium Voltage AC Drives
  • TMEIC TMdrive-50 Medium Voltage AC Drives
  • TMEIC TMdrive-MVe2 Medium Voltage AC Drives
  • TMEIC TMdrive-XL80 Medium Voltage AC Drives
  • TMEIC TMdrive-XL75 Medium Voltage AC Drives
  • TMEIC TMdrive-XL55 Medium Voltage AC Drives
  • TMEIC TMdrive-70e2 Medium Voltage AC Drives
  • TMEIC TMdrive-Guardian Medium Voltage AC Drives
  • TMEIC TMdrive®-10e2 DP DC Drives
  • TMEIC TMdrive-DCe2 DC Drives
  • TMEIC Dynamic VAR Compensation – Dyna-VAR™
  • TMEIC PV Inverters SOLAR WARE 2500
  • TMEIC PV Inverters SOLAR WARE 2700
  • TMEIC PV Inverters SOLAR WARE 3200
  • TMEIC Power Plant Controller
  • TMEIC High-voltage motors 21-L series
  • TMEIC MV Motor & Drive Solutions for Power Generation
  • TMEIC AC Motors Rolling Mills
  • TMEIC TMdrive®-70 Medium Voltage 3-Level IEGT System Drive
  • TMEIC TMdrive®-70e2 Medium Voltage 3-Level IEGT System Drive
  • TMEIC TMdrive-MVe2 Reactive Power Control
  • TMEIC TMdrive®-30 Medium Voltage 3-Level IGBT System Drive
  • TMEIC Unified Controller nv Series
  • DEIF MVR-F215 Product description
  • DEIF MVR-F210 Feeder Protection
  • DEIF MVR-F205 Directional Feeder Protection
  • DEIF PPM 300 Protection & power management
  • DEIF RMC-142D Current relay
  • DEIF GPU-3 hydro Generator protection unit
  • DEIF MVR-200 series Medium Voltage Relay
  • DEIF RMC-131D Current relay
  • DEIF MDR-2 Multi-differential relay
  • DEIF AGC 150 ATS: Advanced Generator Transfer Switch for Seamless Power Management
  • DEIF DVC 350 Digital automatic voltage regulator (AVR)
  • DEIF Digital Voltage Controller DVC 550
  • DEIF TAS-331DG AC transducer for active or reactive power
  • DEIF RMV-112D Undervoltage and overvoltage relay
  • DEIF DPS-1 DC Power Supply
  • DEIF DM 400 hydro Integrated systems
  • DEIF DBC-1 Battery charger
  • DEIF CSQ-3 Multi-function synchroscope
  • DEIF CODESYS Features Software - AWC 500 development package
  • DEIF AMC 300 Advanced Programmable Controller
  • DEIF AGI 400 Advanced graphical interface
  • DEIF BRW-2 & BW Analogue illuminated bridge wing indicators
  • DEIF AWC 500 - G59/3 Integrated G59/3 protection turbine controller unit
  • DEIF AWC 500 Advanced Controller
  • DEIF ASK & ASR Measuring transformer
  • DEIF ASC-4 Battery Automatic Sustainable Controller
  • DEIF ASC plant management Automatic sustainable controller
  • DEIF AOP Additional operator panel
  • DEIF AMC 600 Programmable automation controller with EtherCAT based I/O
  • DEIF AL8-2 Alarm panel
  • DEIF AGC 150 Hybrid Advanced Genset Controller
  • DEIF AGC 150 PMS Lite Simple power management controller
  • DEIF AGC 150 Generator Advanced Genset Controller
  • DEIF AGC 150 Remote Display Remote access and control unit
  • DEIF MVR-250 series Medium Voltage Relay
  • DEIF MVR-210 series Medium Voltage Relay
  • DEIF The SGC series
  • DEIF iE 350 Marine Highly flexible and cybersecure intelligent energy controller
  • DEIF iE 250 Marine Versatile and cybersecure intelligent energy controller for maritime applications
  • DEIF iE 150 Marine Simple and effective power management
  • DEIF iE 650 PLC Extreme robust Programmable Automation controller with EtherCAT based I/O
  • DEIF iE 350 PLC Robust right out of the box
  • DEIF iE 250 PLC Versatile and modular intelligent energy PLC controller
  • DEIF XL / BW / BRW-2 Illuminated indicators
  • DEIF SGC 120/121 Single Genset Controllers
  • DEIF Load Sharing Unit LSU-112DG
  • DEIF Automatic Genset Controller AGC-4