Product Description
The EIOC is a big pipe for the integration of process data from
3rd party Ethernet Devices, such as PLCs and smart field devices
such as Intelligent Field Devices (IFDs) and Intelligent Electronic
Devices (IEDs). A network of these Ethernet Devices can be
directly connected to the EIOC. The Ethernet Devices can
communicate to the EIOC using one of five protocols;
Modbus TCP, EtherNet/IP, IEC61850 MMS, OPC UA client
and EtherNet/IP Control Tag Integration. The EIOC connects
directly into the DeltaV Control Network and can be placed
remotely in an enclosure in the field.
The EIOC is an independent embedded data server. This means
that there is no need for a separate controller to process the
data being integrated into the EIOC. Control Modules needed
to process the data from the Ethernet Devices are assigned and
executed in the EIOC. In this way, communications with the
devices are fast and direct. Any parameters from the modules
running in the EIOC can be read by both S-series and M-series
controllers using External References when needed in control
strategies at the controller level.
When configuring the EIOC Control Modules, all typical
Function blocks needed for continuous operation are available;
however, the usage of the following Function blocks are limited
in the EIOC:
256 DC’s, EDC’s and DCC’s – used for such applications as
motor control in MCCs.
26 PID’s – analog control where all or most of the signals are
coming from Ethernet Devices.
16 SEQs – Sequence function block used for sequencing
motor control states.
16 STDs – State Transition Diagram used in sequencing and
can be used with the SEQ function blocks.
Batch control, SFCs, PLMs, and Equipment Modules are not
supported in the EIOC.
To maintain the capacity of the EIOC, consideration should be
taken to keep modules as lean as possible. Heavy configuration
in the modules will decrease the capacity of 2000 modules in
the EIOC.
Listed by category, the following is a complete list of the
function blocks available with the EIOC.
Advanced Control – None
Advanced Functions – State Transition, Step Sequencer
Analog Control – Analog Tracking, Calc/Logic, Filter,
Input Selector, Scaler, Signal Characterizer, Signal Generator,
Signal Selector, Bias/Gain, Manual Loader, PID, Rate Limit,
Ramp, Enhanced Ramp, Splitter, Limit
Energy Metering – None
IO – Alarm Detection, AI, AO, DI, DO
Tag I/O – DI, DO, AI, AO
Logical – All
Math – All
Special Items – All
Timer Counter – All
Access to DeltaV Live graphics, DeltaV Operate graphics, and
the alarms and history collection from EIOC control modules
follows the same rules and mechanisms as control modules
running in the controllers in a DeltaV System.
The EIOC mounts on the dual horizontal carrier, which includes
redundant Power input Terminals as well as redundant
Ethernet Isolation ports. The Ethernet Isolation ports isolate
the redundant DeltaV Control Network communication
from the redundant Ethernet Device Networks. An Industrial
Networks Firewall is recommended to provide added security
based on deep packet inspection to restrict communications
at the Ethernet device and Ethernet protocol level. In this way,
Robustness and Security is ensured.