Supported Industrial
Ethernet Protocols:
Modbus TCP Interface
The Modbus TCP interface will support Modbus data
sources such as PLCs, MCCs, analyzers and similar devices
communicating Modbus TCP. The Modbus TCP interface is a
Modbus Client reading and writing data from/to Modbus Server
devices. The Modbus server devices can be Modbus TCP devices
or Modbus serial devices using a Modbus TCP gateway.
The Modbus TCP interface supports the following types of
data access:
Reading input data from Modbus Coils, Discrete Input,
Holding Registers, and Input Registers.
Writing output data to Coils and Holding registers.
All reads will be performed periodically and outputs will be
sent when they are written.
EtherNet /IP
The EtherNet/IP protocol allows data sources such as
PLCs, Intelligent Field Devices (IFDs), variable-speed drives,
MCCs, and analyzers; as well as other devices communicating
EtherNet/IP to connect directly in to DeltaV via the EIOC.
The EtherNet/IP interface will support connections for
both implicit and explicit messaging to allow access to both
Class 1 and Class 3 EtherNet/IP I/O adapters. Redundancy with
EtherNet/IP Class 1 Implicit and Class 3 Explicit messaging
for control (sending outputs to the devices) require special
considerations due to exclusive owner communications defined
by the protocol. Please refer to the DeltaV System Planning
Guide for more information. Class 3 PCCC and UCMM with
Logix tags message classes are also supported.
IEC 61850 (MMS)
The IEC 61850 MMS interface will allow data from Intelligent
Electronic Devices (IEDs) such as motor protection relays,
motor starters, motor control centers, switchgear, and similar
MMS-based devices to be integrated into DeltaV. The MMS
interface will be a client reading and writing data from/to the
Intelligent Electronic Device which acts as the server.
The EIOC only supports reading and writing of real time
signals using this protocol. Reading historical data or
Goose applications are not supported.
OPC UA Client
The OPC UA Client in the EIOC provides native client
implementation of a Data Access profile (real time data)
compliant with OPC UA version 1.03. The OPC UA client will
read and write up to 30,000 real time signals coming from
up to 64 OPC UA servers.
EtherNet/IP Control Tag Integration protocol
The EtherNet/IP Control Tag Integration protocol utilizes
EtherNet/IP Class 3 messaging to provide integration with
tag-based PLC data sources. Referencing data by tag name
eliminates the need for register mapping. Read or write up
to 10 signals per tag, and up to 2000 tags per EIOC for a total
of 20,000 signals. The EtherNet/IP Control Tag Integration
protocol supports reading string type signals and read/write
of arrays up to 64 elements each (max 100 arrays per EIOC).
The EtherNet/IP Control Tag Integration protocol supports
integration with ControlLogix and CompactLogix PLCs
utilizing tags.
Parallel Redundant Protocol (PRP)
PRP is a network protocol standard for Ethernet that provides
seamless failover against failure of any network component.
Therefore, it is a great solution when high availability and short
switchover time is required (e.g. electrical monitoring using
IEC 61850 MMS). PRP allows for communications in Primary and
Secondary ports of the Ethernet Device Network in the EIOC to
happen at the same time. This means that a device connected
to the Ethernet Device network is getting the same information
at the same time, through different network paths. In case of
failure in one of the networks it basically provides a zero-time
to recovery (no time to switchover) and eliminates any single
point of failure in a redundant Ethernet Device Network.
PRP is independent of the application-protocol and can be
used by most Industrial Ethernet protocols. In the EIOC,
PRP is an optional feature than can be enabled at the port level
and is available with all the protocols supported in the EIOC.
When enabled, PRP runs on top of the protocol that is selected
at that time.
For PRP to work properly, the Ethernet Devices connected to
the redundant network needs to support PRP natively as well.
If the devices do not support PRP natively, then a RedBox must
be used to allow the connection into the PRP network without
having bad status in diagnostics.
EIOC Configuration
The EIOC is configured in the I/O network level of DeltaV
Explorer and it does not count towards the controller node
count limit (limited to 60 EIOCs per system). The hierarchy
of the EIOC in DeltaV Explorer consist of:
EIOC
z Assigned Modules – Modules configured and running
inside the EIOC.
z Hardware Alarms – Hardware alarms associated with
the EIOC.
z PO1 – EIOC port, where the Ethernet Device Network
and protocol is setup.
z PDT – The Ethernet Devices are added and configured
under the EIOC port as Physical Devices (PDTs).
The amounts of PDTs that can be configured will vary
depending of the protocol selected in the port and
the amount of device licenses assigned. The PDTs can
be renamed.
z LDT – Logical Devices (LDTs) are added under the PDTs to
configure signals or control tags depending of the protocol
that has been selected at the port level. DST licenses are
applied at this level.
EIOC Licensing
Licensing for the EIOC is easy and scalable. Just buy the
hardware assembly for the EIOC, simplex or redundant.
No additional license is required for redundancy. Then decide
which protocol you need (one per EIOC is permitted),
and pick the appropriate license. Next, determine how many
Ethernet Devices you need to connect, and pick the license
containing the required number. Once the EIOC is configured
one DST license will be consumed per LDT, with the type being
determined based on the highest value configured in the LDT
(except for the EtherNet/IP Control Tag Integration Protocol).
For the EtherNet/IP Control Tag Integration protocol,
one DST license is consumed per Control Tag. The DST license is
consumed based on the type of Control Tag that is configured.
PRP does not require a license, as it is included as part of the
EIOC functionality.
Summary
The EIOC supports communications with Ethernet Devices
using Modbus TCP, EtherNet/IP, IEC61850 MMS, OPC UA client
and Ethernet/IP Control Tag Integration protocols. The EIOC
supports a huge capacity of data for monitoring or control.
The Capacity, polling and switchover times vary based on
protocol, device type, and loading. Refer to the DeltaV System
Planning Guide for more information.
The EIOC capacity lends itself to very large integration projects
with limited control needs. For applications that require
batch or sequence control (class-based units, PLMs, SFCs,
and Equipment Modules are not supported in the EIOC)
or more complex control that requires other functionality
such as traditional, bus, or Electronic Marshalling IO, then a
PK controller or a VIM2 card combined with a DeltaV controller
could be a better solution. Please consult your local Emerson
office for more details.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved