A-B 1336 PLUS II Adjustable Frequency AC Drive

From:A-B | author:Mr.Chen | Time :2024-10-26 | 801 view: | 🔊 Click to read aloud ❚❚ | Share:

Electrical Interference - EMI/RFI

Immunity

The immunity of 1336 PLUS II drives to externally generated interfer ence is good. 

Usually, no special precautions are required beyond the installation practices provided in this publication.

It is recommended that the coils of DC energized contactors associ ated with drives be suppressed with a diode or similar device, 

since they can generate severe electrical transients.

Emission

Careful attention must be given to the arrangement of power and ground connections to the drive to avoid interference with nearby sen

sitive equipment. The cable to the motor carries switched voltages and should be routed well away from sensitive equipment.

The ground conductor of the motor cable should be connected to the drive ground (PE) terminal directly. 

Connecting this ground conductor to a cabinet ground point or ground bus bar may cause high frequency current to circulate in the ground system of the enclosure. 

The motor end of this ground conductor must be solidly connected to the motor case ground.

Shielded or armored cable may be used to guard against radiated emissions from the motor cable. 

The shield or armor should be connected to the drive ground (PE) terminal and the motor ground as outlined above.

Common mode chokes at the drive output can help reduce commonmode noise on installations that do not use shielded cable. 

Common mode chokes can also be used on analog or communication cables.

Refer to page 2–37 for further information.

An RFI filter can be used and in most situations provides an effective reduction of RFI emissions that may be conducted into the main supply lines.

If the installation combines a drive with sensitive devices or circuits,it is recommended that the lowest possible drive PWM carrier frequency be programmed.

RFI Filtering

1336 PLUS II drives can be installed with an RFI filter, which controls radio-frequency conducted emissions into the main supply lines and ground wiring.

If the cabling and installation recommendation precautions described in this manual are adhered to, 

it is unlikely that interference problems will occur when the drive is used with conventional industrial elec

tronic circuits and systems. However, a filter may be required if there is a likelihood of sensitive devices or circuits being installed on the same AC supply.

Where it is essential that very low emission levels must be achieved or if conformity with standards is required the optional RFI filter must be used. 

Refer to Appendix C and instructions included with the filter for installation and grounding information.

Grounding

Refer to the grounding diagram on page 2–13. 

The drive must be connected to system ground at the power ground (PE) terminal provided on the power terminal block (TB1). 

Ground impedance must conform to the requirements of national and local industrial safety regulations (NEC, VDE 0160, BSI, etc.) and should be inspected and tested at

appropriate and regular intervals.

In any cabinet, a single, low-impedance ground point or ground bus bar should be used. 

All circuits should be grounded independently and directly. 

The AC supply ground conductor should also be connected directly to this ground point or bus bar.

Sensitive Circuits

It is essential to define the paths through which the high frequency ground currents flow. 

This will assure that sensitive circuits do not share a path with such current.

Control and signal conductors should not be run near or parallel to power conductors.

Motor Cable

The ground conductor of the motor cable (drive end) must be connected directly to the drive ground (PE) terminal, not to the enclosure bus bar. 

Grounding directly to the drive (and filter, if installed) can provide a direct route for high frequency current returning from the motor frame and ground conductor.

At the motor end, the ground conductor should also be connected to the motor case ground.

  • GE Multilin 750-P5-G5-S5-HI-A20-G 750 Management Relay
  • GE Multilin 750-P5-G5-D5-HI-A20-R 750/760 Feeder Mgmt Relay Series
  • GE Multilin 750-P5-G5-D5-HI-A20-G Management Relay
  • GE Multilin 750-P5-G1-D5-HI-A20-R Multilin 1A Zero Sequence Current Inputs
  • GE Multilin 750-P1-G1-S1-HI-A20-R-T-H Feeder Management Relays
  • GE Multilin 750-P1-G1-S1-HI-A20-R Feeder Management Relays
  • GE Multilin 750-P1-G1-D1-HI-A20-R Base Unit 750 Relay
  • GE Multilin 239-RTD-AN-H motor protection relay
  • GE Multilin 489-P5-HI-A20-T-H Generator Management Relay for 489 Series
  • GE Multilin 489-P5-HI-A20-T Generator Management Relay for 489 Series
  • GE Multilin 489-P5-HI-A20-E-H Relay Motor Management
  • GE Multilin 489-P1-LO-A20 489 Motor Management Relay Base Unit
  • GE Multilin SR469-P5-LO-A20-T Motor Management Relay
  • GE Relay from GE Grid Solutions SR469-P5-LO-A20-E
  • GE Multilin SR469-P5-LO-A20 Motor Management Relay with Case
  • GE Multilin SR469-P5-HI-A20-T 469 Series Relay
  • GE Multilin SR469-P1-HI-A1-E-H 469 Series Relay
  • GE Multilin SR469-P1-H1-A1-E 469 Series Relay
  • GE Multilin 469-P5-LO-A20-T Phase Current Input 5 A Phase CT Secondaries
  • GE Multilin 469-P5-LO-A20-E LO Control Power with 4-20mA Analog Outputs
  • GE Multilin 469-P5-LO-A20 Motor Management Relay
  • GE Multilin 469-P5-HI-A20-E-H Motor Management Relay
  • GE Multilin 469-P5-HI-A20 469 Motor Management Relay
  • GE Multilin 469-P1-HI-A1-E-H 469 Base Unit Motor Management Relay
  • GE Multilin 469-P1-H1-A1-E 469 Motor Mgmt Relay
  • Beckhoff ED2504 | EtherCAT Terminal, 4-channel PWM output
  • Beckhoff EL2262 | EtherCAT Terminal, 2-channel digital output
  • Beckhoff EL2258 | EtherCAT Terminal, 8-channel digital output
  • Beckhoff EL2252 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 0.5 A, timestamp
  • Beckhoff EL2212 | EtherCAT Terminal, 2-channel digital output
  • Beckhoff EL2202-0100 | EtherCAT Terminal, 2-channel digital output
  • Beckhoff EL2202 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 0.5 A, push-pull, tristate
  • Beckhoff EL2124 | EtherCAT Terminal, 4-channel digital output, 5 V DC, 20 mA
  • Beckhoff EL2088 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A, ground switching
  • Beckhoff EL2084 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, ground switching
  • Beckhoff EL2068 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A, with channel diagnostics
  • Beckhoff EL2044 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A, with extended diagnostics
  • Beckhoff EL2042 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 2 x 4 A/1 x 8 A
  • Beckhoff ED2034 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A, push-in, with channel diagnostics
  • Beckhoff EL2034 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A, with diagnostics
  • Beckhoff ED2032 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 2 A, push-in, with channel diagnostics
  • Beckhoff EL2032 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 2 A, with diagnostics
  • Beckhoff EL2024-0010 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A
  • Beckhoff EL2024 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 2 A
  • Beckhoff EL2022 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 2 A
  • Beckhoff EL2014 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A, with extended diagnostics
  • Beckhoff ELX2008 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 30 mA, Ex i
  • Beckhoff ED2008 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A, push-in
  • Beckhoff EL2008 | EtherCAT Terminal, 8-channel digital output, 24 V DC, 0.5 A
  • Beckhoff EL2004 | EtherCAT Terminal, 4-channel digital output, 24 V DC, 0.5 A
  • Beckhoff ELX2002 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 45 mA, Ex i
  • Beckhoff EL2002 | EtherCAT Terminal, 2-channel digital output, 24 V DC, 0.5 A
  • TMEIC TM21-TG Series 2-Pole Generator
  • TMEIC TM21-TG Series 4-Pole Generator for Turbine Drive
  • TMEIC Air-Cooled Type Synchronous Generators
  • TMEIC TMdrive-XL85 Medium Voltage AC Drives
  • TMEIC TMdrive-30 Medium Voltage AC Drives
  • TMEIC TMdrive-MVG2 Medium Voltage AC Drives
  • TMEIC TMdrive-70 Medium Voltage AC Drives
  • TMEIC TMdrive-50 Medium Voltage AC Drives
  • TMEIC TMdrive-MVe2 Medium Voltage AC Drives
  • TMEIC TMdrive-XL80 Medium Voltage AC Drives
  • TMEIC TMdrive-XL75 Medium Voltage AC Drives
  • TMEIC TMdrive-XL55 Medium Voltage AC Drives
  • TMEIC TMdrive-70e2 Medium Voltage AC Drives
  • TMEIC TMdrive-Guardian Medium Voltage AC Drives
  • TMEIC TMdrive®-10e2 DP DC Drives
  • TMEIC TMdrive-DCe2 DC Drives
  • TMEIC Dynamic VAR Compensation – Dyna-VAR™
  • TMEIC PV Inverters SOLAR WARE 2500
  • TMEIC PV Inverters SOLAR WARE 2700
  • TMEIC PV Inverters SOLAR WARE 3200
  • TMEIC Power Plant Controller
  • TMEIC High-voltage motors 21-L series
  • TMEIC MV Motor & Drive Solutions for Power Generation
  • TMEIC AC Motors Rolling Mills
  • TMEIC TMdrive®-70 Medium Voltage 3-Level IEGT System Drive
  • TMEIC TMdrive®-70e2 Medium Voltage 3-Level IEGT System Drive
  • TMEIC TMdrive-MVe2 Reactive Power Control
  • TMEIC TMdrive®-30 Medium Voltage 3-Level IGBT System Drive
  • TMEIC Unified Controller nv Series
  • DEIF MVR-F215 Product description
  • DEIF MVR-F210 Feeder Protection
  • DEIF MVR-F205 Directional Feeder Protection
  • DEIF PPM 300 Protection & power management
  • DEIF RMC-142D Current relay
  • DEIF GPU-3 hydro Generator protection unit
  • DEIF MVR-200 series Medium Voltage Relay
  • DEIF RMC-131D Current relay
  • DEIF MDR-2 Multi-differential relay
  • DEIF AGC 150 ATS: Advanced Generator Transfer Switch for Seamless Power Management
  • DEIF DVC 350 Digital automatic voltage regulator (AVR)
  • DEIF Digital Voltage Controller DVC 550
  • DEIF TAS-331DG AC transducer for active or reactive power
  • DEIF RMV-112D Undervoltage and overvoltage relay
  • DEIF DPS-1 DC Power Supply
  • DEIF DM 400 hydro Integrated systems
  • DEIF DBC-1 Battery charger
  • DEIF CSQ-3 Multi-function synchroscope
  • DEIF CODESYS Features Software - AWC 500 development package
  • DEIF AMC 300 Advanced Programmable Controller
  • DEIF AGI 400 Advanced graphical interface
  • DEIF BRW-2 & BW Analogue illuminated bridge wing indicators
  • DEIF AWC 500 - G59/3 Integrated G59/3 protection turbine controller unit
  • DEIF AWC 500 Advanced Controller
  • DEIF ASK & ASR Measuring transformer
  • DEIF ASC-4 Battery Automatic Sustainable Controller
  • DEIF ASC plant management Automatic sustainable controller
  • DEIF AOP Additional operator panel
  • DEIF AMC 600 Programmable automation controller with EtherCAT based I/O
  • DEIF AL8-2 Alarm panel
  • DEIF AGC 150 Hybrid Advanced Genset Controller
  • DEIF AGC 150 PMS Lite Simple power management controller
  • DEIF AGC 150 Generator Advanced Genset Controller
  • DEIF AGC 150 Remote Display Remote access and control unit
  • DEIF MVR-250 series Medium Voltage Relay
  • DEIF MVR-210 series Medium Voltage Relay
  • DEIF The SGC series
  • DEIF iE 350 Marine Highly flexible and cybersecure intelligent energy controller
  • DEIF iE 250 Marine Versatile and cybersecure intelligent energy controller for maritime applications
  • DEIF iE 150 Marine Simple and effective power management
  • DEIF iE 650 PLC Extreme robust Programmable Automation controller with EtherCAT based I/O
  • DEIF iE 350 PLC Robust right out of the box
  • DEIF iE 250 PLC Versatile and modular intelligent energy PLC controller
  • DEIF XL / BW / BRW-2 Illuminated indicators
  • DEIF SGC 120/121 Single Genset Controllers
  • DEIF Load Sharing Unit LSU-112DG
  • DEIF Automatic Genset Controller AGC-4