Description
The 2597 8/16/32-Point DC Discrete Output
Module provides eight, sixteen, or thirty-two
sourcing fused outputs from the CTI 2500
Series or Simatic® 505 I/O base. The module
utilizes solid-state output circuits to switch on
or off external devices such as pilot lamps,
motor starters, or solenoids. The 2597 is
designed to switch externally supplied 11-125
VDC. The internal logic signals are isolated
from the external outputs to 2100 VDC.

Features
• 8. 16. or 32 DC output points
• Replaces Siemens® 505-4508. -4516. -4532.
-4708. -4716. -4732
• 3000 VDC group-to-group isolation
• 2100 VDC channel-to-backplane isolation
• Isolation in groups of 4 or 8 (selectable with
32 pt login configuration
• Wide 11-125 VDC output range
• 2A per output, 8A per user power input
• 32 Amps total module output
• Individually sourcing fused outputs
Specifications
Outputs per Module: 8.16. or 32
Isolation: 2100 VDC channel-to-backplane
3000 VDC group-to-group
Output Voltage: 11 VDC to 125 VDC
Output Source Current per Circuit:
2.0 Amps max., 1 mA min.
Total Module Output Current: 32 Amps max.
from 0o to 60oC
Maximum Surge Current: 3 Amps for 15 Sec
“ON” State Voltage Drop: 0.5V @ 1.0 Amp
“OFF” State Leakage Current: <20µA
Turn On Time: 1 mSec (nominal)
Turn Off Time: 3 mSec (nominal)
Fuses: 32. 2.5 amp, 250V,
Type: Littlefuse #21602.5.
Bussman GDA-2.5 (Field replaceable)
Connector: Removable
Wire Gauge: 14 - 22 AWG
Backplane Power: 1.7 Watts max.
Module Size: Single-wide
Operating Temperature: 0o to 60oC
(32o to 140oF)
Storage Temperature: -40o to 85oC
(-40o to 185oF)
Relative Humidity: 5% to 95%
(non-condensing)
Agency Approvals Pending:
UL, ULC, FM (Class 1. Div.2), CE
Shipping Weight: 1.5 lb. (0.68 Kg)
32-Point Mode: 4 Common Configuration
The user may configure the module to allow four channels to be grouped and share a common field user
power, thereby allowing a different user power supply voltage to be used by each grouping. Jumpers J2.
J4. J5. and J6 are used to configure this selection.
For example, if the user places the J2 jumper in the 4 Common position, Channels 1-4 will share a
common user power and Channels 5-8 will share another common user power. In this example each
group of four channels is isolated from the other group of four channels. Because each group of four is
isolated, the user may also change the supply voltage for each group. So, in this example, Channels 1-4
could be 24VDC outputs and Channels 5-8 could be 60VDC outputs. Furthermore, the user may select a
different configuration for J4. J5. or J6. allowing for further combinations of four or eight channels that
share a common.