Description
The 2598 8/16-Point AC Discrete Output Module
provides eight outputs isolated in groups of 2 from
CTI 2500 Series® or Simatic® 505 I/O bases. The
module utilizes solid-state output circuits to switch on
or off external devices such as pilot lamps, motor
starters, or solenoids. The 2598-8 is designed to
switch externally supplied 11 to 240 VAC. The internal
logic signals are isolated from the external outputs to
2100 VDC.

Features
• 8 AC output points
• Replaces Siemens® 505-4608. and -4808.
• 3000 VDC group-to-group isolation
• 2100 VDC channel-to-backplane isolation
• Isolation in groups of two
• Wide 11-240 VAC output range
• 2.0 Amps per output
• 16 Amps total module output
• Individually fused outputs
• Sourcing outputs
• Single-wide module
Specifications
Outputs per Module: 8
Isolation:
2100 VDC channel-to-backplane
3000 VDC group-to-group
Output Voltage: 11 VAC to 240 VAC
Maximum Output Current:
2.0 Amps max.,
4A per group
16A per module
For Class 1 Div 2 locations:
2A per point @50°C
1.5A per point @ 60°C
Maximum Surge Current: 3 Amps for 15 Sec
“ON” State Voltage Drop: 1.0V @ 1.0 Amp
“OFF” State Leakage Current: 1mA
Turn On Time: 1 AC cycle
Turn Off Time: 1 AC cycle
Fuses:
16. 2.5 amp, 250V, Type: Littlefuse #21602.5.
Bussman GDA-2.5 (Field replaceable)
Connector: Removable Part# 2500-40F
Note: The connector is ordered separately.
Wire Gauge: 14 - 22 AWG
Backplane Power: 1.25 Watts max.
Module Size: Single-wide
Shipping Weight: 1.5 lb. (0.68 Kg)
Channel Configuration Explanation
The 2598-8 was designed using a PCB that could also perform as a 16 or 32pt module.
Hence, the PCB printing for channels do not line up with actual 2598-8 channels.
See chart below for the proper correlation of channels.
For example, if the module reported channel 4 was blown, then the user would replace
the fuse marked ‘CH 10’ on the PCB.
Grouping Configuration
The 2598-8 is shipped to allow two channels to be grouped and share a common field
user power, thereby allowing a different user power supply voltage to be used by each
grouping. Jumpers J2. J4. J6. and J8 come set in the “8 common” selection from the
factory and should not be altered for proper module operaton. This setting allows for
2 points per common operation.
For example, Channels 1-2 will share a common user power and Channels 3-4 will share
another common user power. In this example each group of two channels is isolated
from the other group of two channels. Be-cause each group of two is isolated,
the user may also change the supply voltage for each group.
So, in this example, Chan- nels 1-2 could be 240VAC outputs and Channels 3-4 could
be 120VAC outputs.