Description
The 2596-8 8 Point DC Discrete Output Module
provides eight sourcing fused outputs from the CTI
2500 Series® or Simatic® 505 I/O base. The module
utilizes solid-state output circuits to switch on or off
external devices such as pilot lamps, motor starters,
or solenoids. The 2596-8 is designed to switch
externally supplied 11-125 VDC.

Features
• 8 DC output points
• Replaces Siemens® 505-4508. -4708
• 3000 VDC group-to-group isolation
• 2100 VDC channel-to-backplane isolation
• Isolation in groups of two
• Wide 11-125 VDC output range
• 2.0 Amps per output
• 16 Amps total module output
• Individually sourcing fused outputs
• Single-wide module
Specifications
Outputs per Module: 8
Logon: 8Y
Isolation:
2100 VDC channel-to-backplane
3000 VDC group-to-group
Output Voltage: 11 VDC to 125 VDC
Output Source Current per Circuit:
2.0 Amps max., 1 mA min.
Total Module Output Current:
16 Amps max. from 0° to 60°C
Maximum Surge Current: 3 Amps for 15 Sec
“ON” State Voltage Drop: 0.5V @ 1.0 Amp
“OFF” State Leakage Current: <20µA
Turn On Time: 1 mSec (nominal)
Turn Off Time: 3 mSec (nominal)
Fuses: 8. 2.5 amp, 250V,
Type: Littlefuse #21602.5.
Bussman GDA-2.5 (Field replaceable)
Connector: Removable 40 Pin Connector
(ordered separately CTI Part # 2500-40F)
Wire Gauge: 14 - 22 AWG
Backplane Power: 1.0 Watts max.
Module Size: Single-wide
Shipping Weight: 1.5 lb. (0.68 Kg)
Additional Product Information:
On CTI’s Website you will find links to the 2500
Series Std Environmental Specifications and the UL
Agency Certificates of Compliance.
Login 8/16 Point Configuration Explanation
The 2596-8 was designed using a PCB that could also perform as a 16 or 32pt module.
Hence, the PCB printing for channels do not line up with actual 2596-8 channels.
See the chart below for the proper correlation of channels.
For example, if the module reported channel 4 was blown, then the user would replace
the fuse marked ‘CH10’ on the PCB.
Grouping Configuration
The 2596-8. two channles are grouped together
and share a common field user power, thereby
allowing a different user power supply voltage to
be used by each grouping. Jumpers J2. J4. J5.
and J6 are set in the “8 Common” selection from
the factory and, for proper module operation,
should not be altered. This setting allows for 2
points per common operation.
For example, Channels 1-2 will share a common
user power and Channels 3-4 will share another
common user power. In this example each group
of four channels is isolated from the other group
of four channels. Because each group of four is
isolated, the user may also change the supply
voltage for each group. So, in this example,
Channels 1-2 could be 24VDC outputs and
Channels 3-4 could be 60VDC outputs.