Description
The REF601 is a dedicated feeder protection and control relay.
The REJ601 is an overcurrent protection relay without breaker control.
These relays are intended for the protection of utility
substations and industrial power systems within primary and
secondary distribution networks. They are members of ABB’s
Relion® product family and part of its 605 series.
These relays, provide an optimized composition of protection,
monitoring and control functionality in one unit, with the best
performance usability in its class and are based on ABB’s indepth knowledge of protection and numerical technology
Relay functions
The REF601 and REJ601 can be pre-configured which facilitates easy and fast commissioning of switchgear.
To emphasize the simplicity of using these relays, only application specific parameters need to be set within the relay’s intended area of application.
The standard signal configuration can be altered by LHMI (local human-machine interface).
The relays are available in three alternative application configurations, as indicated in Table 2.
Protection functions
The REF601 and REJ601 offer three-stage overcurrent and twostage ground-fault protection functions.
The transformer inrush detector function is incorporated to prevent unwanted tripping due to energizing of transformers.
The REF601 and REJ601 offer three-stage overcurrent and
two-stage ground fault protection functions.
The low-set stages for overcurrent and ground fault protection are equipped with
selectable characteristics – Definite Time (DT) and Inverse Definite Minimum Time (IDMT).
The relays feature standard IDMT characteristics according IEC 61255-3 - Normal Inverse, Very
Inverse, Extremely Inverse, Long-time Inverse.
They also feature characteristics according to ANSI C37.112 - Moderate Inverse,
Normal Inverse, Very Inverse, and Extremely Inverse.
The relays also have a special characteristic RI Inverse (RI) for better coordination with the rest of the network.
Additionally the relays also support two setting groups.
The REF601 and REJ601 also offer thermal overload protection for feeders, cables and transformers.
Other protections include negative phase sequence protection, phase discontinuity
protection and circuit breaker failure protection.
The relays also have an auto-recloser option for overhead line feeders.