Overview
REF601 CEI overview
REF601 is a dedicated feeder protection relay, intended for the protection, measurement and supervision of utility substations and industrial power systems.
Engineered from the ground up, the relay is inspired by and is compatible with the Rogowski coil sensor for current measurement.
The new feeder protection relay is designed to unleash the advantages of current sensors for protection and control in medium voltage applications.
The REF601 features compact size and ease of use.
The features include:
. Sensor input for phase current
. External CBCT input for earth current
. Three-stage overcurrent protection
. Two-stage earth-fault protection
. Magnetizing inrush detection
. Control of circuit breaker
. Local and remote control
. Five event logs
. Two fault records of analogue value
. Non-resettable trip counter
. On-line measurements
. Comprehensive local HMI
. Universal auxiliary supply rating
. Circuit breaker or panel mounting
. Optional Modbus communication
. Non-volatile memory
. Access control
. Self-supervision
. Built-in test functionality
Basic Functions
Self Supervision
The IED is provided with an extensive self-supervision system which continuously
supervises the software and the electronics. It handles run-time fault situations and
informs the user about an existing fault via the LHMI and the communication.
When in an IED internal fault is detected, the green Ready LED ceases to glow and the
self-supervision output contact is activated. Internal fault indications have the highest
priority on the LHMI. None of the other LHMI indications can override the internal fault
indication. An indication about the fault is also shown as a message on the LHMI.
The text IRF with an additional text message, a code is shown to indicate the fault type.
The user can try to eliminate the fault by restarting the IED.
If the fault is still found, the IED stays in internal fault mode.
All other output contacts are released and locked for the internal fault.
The IED continues to perform internal tests during the fault situation.
If an internal fault disappears, the green Ready LED starts glowing and the IED
returns to the normal service state. The fault indication message remains on the LCD until manually cleared.
The self-supervision signal output operates on the closed circuit principle.
Under normal conditions the relay is energized and the contact gap 5-6 in connector XK2 is closed.
If the auxiliary power supply fail or an internal fault is detected, the contact gap 5-6 is opened.