Standardized configuration
REB611 is available in one configuration.
To increase the user-friendliness of the configuration and to
emphasize the relay's simplicity of usage, only the application
specific parameters need setting within the relay's intended area of application.
The standard signal configuration can be altered by local HMI,
Web HMI or optional application functionality of Protection and
Control IED Manager PCM600.
Protection functions
REB611 offers phase-segregated (three phases) high
impedance differential protection and non-directional earth
fault protection for busbars, motors and generators. The relay
also offers high-impedance differential-based restricted earth
fault protection for motors, generators, reactors and power
transformers. REB611 is ideally suited for backup protection.
Application
REB611 offers bus-differential protection in a single zone with
bus-wire supervision. It also offers the possibility for bus
differential protection over two zones using two REB611 relays.
The combined restricted earth-fault and residual earth-fault
protection functionalities of the relay enable its use in the
protection of a motor or generator. Due to the individuality of
the high-impedance protection functions, a single relay can be
used for restricted earth-fault protection of both the high and
low voltage sides of a power transformer.