Application
The high-impedance principle for busbar differential protection
provides a secure and dependable protection scheme against
faults within the measured zone. The high-impedance principle
has been used for many years for differential protection due to
the capability to manage through-faults also with heavy current
transformer (CT) saturation.
The relay's high-impedance protection functions contain a
built-in blocking functionality, which is provided by the bus-wire
supervision functions to restrict faulty operations in case of
faults in the measurement circuits.
Additional standby (residual) earth-fault protection is provided
by the two non-directional earth-fault stages. The standby
earth-fault protection can be used together with the high
impedance protection functionality to protect motors,
generators and transformers against residual earth faults. The
measurements are taken from the earthing point of the protected object.
The residual earth-fault protection can also be used as bus-wire
supervision especially in new or retrofitting applications where
an earth-fault protection function is used for grounding the
measurement circuits where a short circuit or a break has
occurred. The grounding can be done by an external relay.