Description
Relay modules may be programed to actuate based on
alarm conditions defined in other modules. Use standard
logic elements (True AND, Normal AND, OR and NOT) to
combine various alarms and statuses (e.g. OK statuses,
Bypass, Protection State, Inhibit, Attention, Protection Fault,
etc.) into relay activation conditions. Orbit Studio is used to
program the voting logic.
Relays can operate as a system or group protection fault
relay, if programmed to do so, especially when the protection
fault relay on the SIM does not provide adequate granularity
of system health - typically for multiple machines in one system.
Pairs of relays within the module function as a single Double
Pole, Double-Throw relay when appropriately configured.
Both relay types are available for SIL system implementation.
See Orbit 60 SIL User Guide (134M0398) for additional details
and design considerations.
Electromechanical Relay (EMR)
This relay drives a load directly, or through, an interposing
relay. This module takes two slots. It features 8 Epoxy Sealed,
Single-Pole Double-Throw Electromechanical Relays. This
module supports an AC voltage range of 5-250 Vac for loads
of 100 mA to 4 A. The module also supports DC voltages and
loads of 5-30 Vdc at 4 A.
Solid State Relay (SSR)
This relay connects to an external system’s discrete input for
low current communication. It occupies a single slot and
features 8 Solid-State Relays. This module supports
secondary voltages from 1 Vdc up to 125 Vdc
and loads of 0.01 to 125 mA.