| Item | Specifications |
|---|---|
| Input Frequency | 50‑400 Hz single‑phase |
| Nominal AC Input | 60 Vac / 120 Vac / 240 Vac (jumper selectable) |
| Power Consumption | 85 Watts |
| DC Field Output Rating | 32 /63 /125 Vdc @ 36 Adc |
| Operating Temperature | ‑40 °C ~ +70 °C |
| Humidity | Up to 98% non‑condensing |
| Shock / Vibration | 15 G shock, 2 G (10‑500 Hz) vibration |
| Weight | MVC‑236:6.8 kg; Spike suppression module:608 g |
Frequently Asked Questions (FAQ)
Q: What is MVC 236 used for?
A: MVC‑236 acts as manual backup excitation unit for generator AVR. It takes over control when automatic voltage regulator fails.
Q: Can MVC 236 work without AVR?
A: Yes. It can run standalone for manual generator excitation, bench test procedure is documented inside manual.
Q: Is spike‑suppression‑module always required?
A: Mandatory when power comes from PMG permanent‑magnet‑generator or isolation‑transformer, to suppress inductive voltage spikes.
Q: Can I repair the PCB board inside MVC236?
A: Not recommended, conformal protective coating is applied. Replace the complete PCB assembly instead of component‑level repair.
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2026 Cld , All Rights Reserved K-JIANG All rights reserved