Product Overview
MVC 236 (Manual Voltage Control) manufactured by Basler Electric, is a SCR‑based manual excitation backup controller for generator automatic voltage regulators (AVR). When the main AVR fails, MVC236 takes over generator field excitation and allows operators to manually adjust generator output voltage. Document reference: Instruction Manual Rev K2. document number 9204300990.
MVC236 features integrated build‑up circuit for reliable generator voltage build‑up during start‑up. It is designed for behind‑panel cabinet‑mount installation for stationary generator sets.

Part Number Variants
- 9204300100: MVC236 with mild‑steel chassis
- 9204300104: MVC236 with 316 stainless‑steel chassis for corrosive environment
Standard Supplied Items
- Remote 10 kΩ 1‑W voltage‑adjust potentiometer (Basler P/N 21565)
- Spike suppression module, for PMG / isolation‑transformer high‑impedance power source
Optional Accessories
| Part Number | Description |
|---|---|
| 9204306100 | Auto‑Off‑Manual transfer switch for AVR‑MVC236 switching |
| 9204304100 | Nulling chassis for bumpless transfer between AVR and MVC‑236 |
Core Working Principle
MVC236 uses SCR silicon‑controlled‑rectifier bridge to supply adjustable DC field voltage for generator exciter field.
1. Build‑up Circuit: Provides maximum excitation output during generator startup. After generator voltage rises above ~30 Vac, manual potentiometer takes charge of excitation regulation.
2. Jumper‑selectable input AC power: 60 Vac /120 Vac / 240 Vac.
3. Jumper‑selectable frequency range: 50‑100 Hz /100‑200 Hz /200‑400 Hz.
4. Jumper‑selectable DC field output: 32 Vdc, 63 Vdc, 125 Vdc @ 36 Adc nominal.
5. Spike‑suppression module absorbs destructive voltage spikes, mandatory for PMG and isolation‑transformer feeding scenarios.
Mechanical & Installation Requirements
1. Vertical‑only mounting: Vertical installation is mandatory for sufficient heat dissipation. Max mounting depth: 4.375 in (111 mm).
2. Operating ambient temperature: ‑40 °C ~ +70 °C, storage temperature ‑40 °C ~ +85 °C.
3. The potentiometer and spike‑suppression module have separate mounting drawings with inch‑metric dual dimension.
4. Shock resistance: 15 G three‑axis shock; vibration rating: 2 G 10‑500 Hz.
Wiring Guidance
> Caution: Do NOT apply high‑potential hipot test incorrectly, mis‑application will permanently damage internal SCR modules.
- Input power connects to TB2‑23. TB2‑24. external fuse protection is required.
- Select input AC tap via TB2‑TAP jumper:60 /120 / 240 Vac.
- Select DC field output via TB1‑COM jumper: 32 Vdc / 63 Vdc /125 Vdc.
- Frequency range selection via TB1‑COM(Hz) jumper; remove jumper for 200‑400 Hz.
- Remote manual‑adjust potentiometer connects to TB1‑14.15.16.
- Full application schematic includes AVR interconnection diagram and null‑meter bumpless‑transfer wiring.
Operation & Functional Test
Switch Position (with optional Auto‑Off‑Manual switch)
- Manual: MVC236 controls generator excitation, AVR disconnected.
- Auto: Original automatic voltage regulator controls generator field.
- Off: Generator excitation fully de‑energized.
> Safety Warning: Terminals on AVR side may remain live even under Manual / Off mode. Never remove AVR while generator is running.
Off‑line Operational Bench Test
Users can perform bench test without real generator. Apply 120 Vac input power, connect resistive lamp‑load on field output. Rotate potentiometer and verify lamp brightness changes linearly across 32 /63 /125 Vdc tap settings to validate MVC‑236 hardware health.
Maintenance & Troubleshooting
1. Periodically clean dust and moisture, check tightness of all terminal connections.
2. PCB board is coated with conformal coating. Do NOT repair circuit board locally; replace whole PCB assembly upon failure.
3. Complete spare‑part list includes PCB assembly, SCR power modules, fuses, potentiometer, transformer and spike‑suppression‑module with Basler official part‑numbers.
4. Step‑by‑step troubleshooting flowchart guides technicians to isolate faults: wiring error, transfer‑switch failure, blown fuses, defective MVC236 unit or defective AVR.
Full Technical Specifications