Load Control
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The MSLC-2 has four load control modes available:
• Base load
• Import/export
• Process
• Utility unload
Load control begins with the breaker closure of the utility and another discrete input selecting the load
control mode wanted. If no load control mode is selected the MSLC-2 will be in the offline mode. The
system load immediately prior to breaker closure is used as the starting base load reference. On com
mand, the adjustable ramp allows smooth, time controlled loading into a set import/export level. A ramp
pause switch is provided to stop the ramp at any point.
The import/export control is an integrating control. It adjusts the percentage of rated load carried by the
individual generators, operating in isochronous load sharing, in order to maintain a set import/export or
base load level. The MSLC-2 will maintain a constant base load or import/export level even with chang
ing utility frequencies. The MSLC-2 provides switch inputs to allow raising or lowering the internal digi
tal base load or import/export reference. The control also provides a remote analog signal input for ref
erence setting, if desired. (Signal variety: 0 to 20 mA, 4 to 20 mA, 0 to 5 V, 1 to 5 V and 0 to 10 V)
The MSLC-2 is equipped with a utility unload switch, which provides an adjustable time controlled ramp
to lower the base load or import/export level. When the level is below an adjustable threshold, the
MSLC-2 issues a breaker open command to separate the utility from the local bus. The ramp pause
switch can be used to stop the utility unload at any point. The maximum load that the MSLC-2 can tell
the individual generators to carry is their rated loads. So, in the event that the plant load is greater than
the capacity of the operating generators, the utility unload will stop when 100% rated load is reached
on each of the operating generators. This prevents accidental overloading of the local generators.
The MSLC-2 also includes two adjustable load switches which can be used for external functions or
warnings when chosen system load levels are attained. The high and low limit switches may also be
activated when 100% or 0% load signal to the generators is reached.