DSLC-2 equipped generators
Additional MSLC-2 functions include:
• Automatic dead bus closure capability for tie-breakers
• Multiple utility breaker and tie-breaker MSLC-2s on the same bus segment
• One dedicated Ethernet line for precise system communications between all DSLC-2s and
MSLC-2s on the system
• Ethernet Modbus/TCP for remote control and monitoring
• Serial Modbus RS-485 for remote control and monitoring
• Applications with up to 32 DSLC-2 and 16 MSLC-2
• Automatic segment control (self-recognizing of the segment)
• Full setup, metering and diagnostic capability through the PC program ToolKit
Synchronizer
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Either phase matching or slip frequency synchronizing may be selected. Phase matching provides
rapid synchronizing for critical standby power applications. Slip frequency synchronizing ensures that
the initial flow of power will be either out of the local system (export) or into the local system (import),
depending on whether a positive or negative slip is chosen. For both synchronizing methods, the
MSLC-2 uses actual slip frequency and breaker delay values to anticipate an adjustable minimum
phase difference between the utility and the local bus. Additional synchronizer functions include volt
age matching, time delayed automatic multi-shot reclosing, auto-resynchronizing and a synchronizer
timeout alarm. Each of these features may be enabled or disabled during setup.
The MSLC-2 control provides a safe automatic dead bus closure function. Deadbus closing permission
is granted to only one DSLC-2 or MSLC-2 control in the whole system through locking techniques done
over the communications network.
The MSLC-2. configured as tie-breaker control, allows selecting different closure modes or all modes:
• Alive bus A -> dead bus B
• Dead bus A -> dead bus B
• Alive bus B -> dead bus A