• Accurate, independent controls require
no additional instrumentation for field setting
• Various ∆V and ∆F limits available
• Breaker closing times are field programmable
• 50 Hz operation available

Inputs
Gen/Line Voltage, nominal 120 V ac, 145 V ac maximum continuous. Will withstand 200 V ac for 1 sec.
Bus Voltage, nominal 120 V ac, 145 V ac maximum continuous. Will withstand 200 V ac for 1 sec.
Supply Voltage, minimum 100 V ac, maximum 140 V ac.
Enable Auto-Sync close.
Breaker Closing Time; field programmable from 20 to 800 ms.
NOTE: Gen/Line, Bus and Supply voltages are transformer-isolated to allow complete freedom in
applications.
Burden
Gen/Line or Bus: 0.5 VA maximum at 120 V ac
Supply: 7 VA maximum at 120 V ac
Controls
UPPER VOLTAGE LIMIT (either input): 110 to 140 V ac, accuracy 1–1/2% of full scale
LOWER VOLTAGE LIMIT (either input): 90 to 120 V ac, accuracy 1–1/2% of full scale
∆V LIMIT (MAXIMUM VOLTAGE DIFFERENCE LIMIT): 1 to 5 V ac, accuracy 5% of full scale. Multiples of
this range are available. A ∆V LIMIT of 4 to 20 V ac or lower must be specified if the M-0193B is to be used
in conjunction with the M-0194 Generator Control Unit.
∆F LIMIT (Maximum Frequency Difference Limit): 0.05 to 0.5 Hz, accuracy 3% of full scale. An additional
range of 0.005 to 0.05 Hz is available.
LED Indicators
These LEDs are lit when conditions are met to close the breaker:
• Bus Upper Voltage Limit OK
• Gen/Line Upper Voltage
Limit OK
Breaker Close Relays
• Bus Lower Voltage Limit OK
• Gen/Line Lower voltage
Limit OK
• ∆V Limit OK
• ∆F Limit OK
• M-0193B Ready
Dry output contacts rated to make and carry 20 A up to 250 V dc, interrupt 0.9 A, 120 V dc inductive load;
0.4 A, 250 V dc inductive load. Open contacts or contacts to ground will withstand 1500 V ac for one minute.
Status Contacts
Relay contacts; closed indicates ∆F conditions OK
Relay contacts; closed indicates ∆V conditions OK
These are light duty contacts intended primarily for status interrogation by supervisory control They can be
used to light local lights with the following maximum restrictions: 1/2 A at 125 V dc resistive, 1 A 120 V ac,
250 V dc across open contacts
Minimum Frequency Difference
The guaranteed minimum frequency difference for operation is 0.0005 Hz; however, typical units consistently
operate with frequency differences of 0.0001 Hz.