Huge processing capacity. Each EIOC is capable of handling
a huge amount of Data in up to 2000 Control Modules.
EIOC is part of the DeltaV Control Network. 60 EIOC’s
can be added directly to the DeltaV Control Network,
allowing maximum freedom in segregating your networks.
Flexible networking. User configurable IP addressing for
the Ethernet Device Network allows the EIOC to be used in
almost any plant environment regardless of the networking
scheme. When designing a simplex Ethernet Device Network,
consider that the EIOC and the Ethernet Devices must be on
the same IP subnet to communicate. Also, when designing
a redundant Ethernet Device Network, consider that the
primary and secondary ports in the EIOC must be in different
subnets to follow best engineering practices.
Easy to use. The EIOC is easy to use as it provides a native
way to bring Ethernet protocol data into the DeltaV system.
Specific ease of use features include:
• You can choose between the 5 different Ethernet
protocols supported in the EIOC. Only one protocol is
supported at a time and requires the proper licensing.
• Updates for the EIOC and drivers are included
within DeltaV.
• Configured in DeltaV Explorer. All needed configuration
for the Ethernet Devices is done in DeltaV Explorer and
DeltaV Control Studio, just like Traditional I/O signals.
The data can be configured in DeltaV Control Modules,
displayed on DeltaV Live and DeltaV Operate graphics,
and stored in the DeltaV Continuous Historian.
Modular and Easy to add Redundancy. The dual horizontal
carrier hosts all the needed components for a redundant
setup (redundant Power input Terminals and redundant
Ethernet Isolation ports). The EIOC becomes redundant
just by adding a second EIOC on the dual horizontal
carrier. The configuration will change automatically,
confirming that the two EIOCs are now working as a
redundant pair. Manual switchovers can be controlled
in DeltaV Diagnostics Explorer. The redundant Ethernet
ports provide isolation between DeltaV Control Network
communication and the redundant Ethernet Device Network.
The EIOC also implements Parallel Redundant Protocol
(PRP) for an added layer of robustness, providing a seamless
switchover between primary and secondary networks.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved