Product Description
The I/O interface carrier plugs on to the power/controller
carrier. The power/controller carrier supplies the system
power and communications between the I/O interfaces and
the controller. The controller processes the I/O interface
information. An additional power/controller carrier is required
for use with redundant controllers.
Mount your interface carrier on a T-type DIN rail. The I/O
interface carrier includes the connections for the bulk 24 V DC
field instrument power, I/O interfaces, and terminal blocks.
Each I/O interface carrier is equipped with a connector that
allows an additional I/O interface carrier to be plugged on to it.

Up to 64 I/O interfaces on eight 8-wide I/O interface carriers are
supported by a single I/O subsystem. For the horizontal-mount
solution, 1-wide local bus extenders allow you to continue
the I/O bus on a different row of carriers. There are two types
of 8-wide I/O interface carriers available. They both have
connectors for field power on the top of the carrier. The original
carrier connects each set of field power terminals to two I/O
cards, and the other option have individual field power per card
slot and is ideal if separate field power is required for redundant
I/O cards.
With the introduction of DeltaV SIS the left one-wide
and right one-wide dual carrier extenders have two,
44-pin D- Shell connectors which supports dual cables for
a fault tolerant configuration. The A and B connectors are
in parallel so either port may be used. The new dual carrier
extenders are a pre-requisite for DeltaV SIS as these also
provide extension of the redundant safety bus used by the
Safety Logic Solvers. The VerticalPLUS mount carriers also
support dual cables and can be used with DeltaV SIS.
Refer to the new VerticalPLUS Carrier Product Data Sheet
for more details on these new carriers.
The horizontal carrier family also offers a 2-wide power carrier.
Use this carrier, along with one or two system power supplies to
provide 12 V DC local bus power connected through the carrier
extenders. There are two 12 V DC output connections powered
by either supply. For redundant power, ensure that the power
demand is within the output range of one system power supply.
With the introduction of the PK controller, a 4 wide I/O carrier
is available for use with M-series I/O cards when a smaller
footprint for the hardware is required. The 4-wide carrier
allows for individual field power per card slot and is ideal
if separate field power is required for redundant I/O cards.