Compatible with previous versions of
DeltaV systems
Switches are compatible with existing systems that are
installed using only our supported Cisco or Hirschmann
switches. Fiber communications of the Smart Switch will
only communicate at 100/1000MB full duplex (not
configurable) and wired ports will only auto-negotiate
communications (setting is not user adjustable).
Existing switches must be configured to run either in auto
negotiate mode or 100/1000MB full duplex communications.
Existing 3COM switches and media converters may not be
compatible with the DeltaV Smart Switch as they may not
support the required communications. The Smart Switch
will not plug and play in some older networks unless the
existing devices are set to match the specifications above
during the installation.
The auto switch lockdown is compatible only with DeltaV v10.3
and later revisions.
Compatible with non-DeltaV Switches
The DeltaV Smart Switch also can be installed in a new system
mixed with the currently supported and shipping Cisco or
Hirschmann switches.
Please read DeltaV Books-on-line for important information
when retrofiting into existing DeltaV networks, especially in
systems with existing 3COM switches or media converters.
Fiberoptic connections on DeltaV Smart Switches are non
configurable and communicate only at 100Mbps on the DeltaV
ACN or 1Gbps switch-to-switch at full duplex.
Installing DeltaV Smart Switches into systems with existing
fiberoptic devices that are not set to 100/1000Mbps full duplex
will cause communications disruptions in the network.
Use outside of the DeltaV Control Network
The DeltaV Smart Switches is supported only as an unmanaged
switch if installed in networks outside of the DeltaV control
network, the DeltaV 2.5 network between the DeltaV
workstations and the perimeter firewall (such as the Emerson
Smart Firewall), or other DeltaV networks external to the DeltaV
control network. The switch will only accept a management
port network address from the DeltaV Network Device
Command Center and the switch can only be used where this
application is able to access the switch.
The DeltaV Smart Switches is not available for use as a managed
switch in the DeltaV InterZone network as the DeltaV Network
Device Command Center cannot access the switch if located on this network.