Some of the events that can cause a switchover are:
•Hardware failure within the active controller
•Communications failure between the active controller and I/O
•Communications failure on both control network ports of the
active controller
•Removal of the active controller from the carrier
•User request initiated from Diagnostic Explorer
System Compatibility
M-series, S-series and SZ controllers are all supported on
DeltaV v12.3 and beyond. PK Controllers are supported on
DeltaV v14.3 and beyond. For detailed version compatibility
see the Prerequisites section below.
Redundant controller pairs must be of the same series. For
example, M-series and S-series controllers cannot be connected
together as a redundant pair.
Although an SX controller can operate as a standby controller to an
SQ active controller, it is recommended that both the active and
standby controllers be of the same hardware. The SQ may not have
sufficient memory or CPU capacity to accept the configuration that
runs in an SX controller. This applies for MX and MQ controllers as
well, only mix controller types as a temporary condition during a
hardware upgrade.
The MQ, MX, SQ, SX and PK Controllers are all capable of
redundancy. For more information on these controllers, refer to
the respective controller product data sheet.
SZ Controllers are also capable of redundancy. For more
information on this controller, refer to the DeltaV SIS Electronic
Marshalling or DeltaV SIS IS Electronic Marshalling product data sheets.