OPERATING MODES
Isolated Bus — The DSLC talks over its LON to share
proportional real and reactive loads. Real load (kW) is
controlled using percentages of full load for each machine,
and reactive loads (kVAR) are
shared by matching power factors.
The DSLC maintains a specified
bus voltage and frequency while
balancing loads.
Utility Parallel — The DSLC
measures real load (kW) on the
generator and adjusts the speed
control to match a set base load, to
control a process at a user-chosen,
externally adjustable setpoint. Or it
can set a constant import/export
level using an MSLC ( Master
Synchronizer and Load Control).
The DSLC can also measure and
maintain a set reactive load (kVAR)
or can maintain a user-prescribed
power factor.
Transition Between Modes — The
DSLC will ramp at a user-chosen
rate from one mode to another
until the control is within 5% of its
target. It then shifts into dynamic
control, allowing bumpless
operating mode changes. In
addition, the DSLC automatically
changes its VAR/PF mode when
the real load mode is changed to or
from an isolated bus, load sharing
mode. Manual VAR/PF control
may also be selected.