Eaton’s BushingGard Predictive Diagnostic solution uses predictive
diagnostics to help users prevent malfunctions or breakdowns in
large power transformer bushing equipment. The self-operating
systems and remote monitoring services provide real-time detection
and allow users to work towards solving problems instead of finding
them. The bushing sensor requires minimum resources, accounts for
minimal outage time, allows for onsite communication, and results in
faster and easier installation.

Core features
• Suitable for use with any condensing type bushing found in transformers,
circuit breakers, shunt reactors, etc. With the InsulGard, it can be used to
detect partial discharge in systems above 38KV.
• All monitoring, necessary sensors, recording equipment and diagnostic
software are non-invasive, which eliminates downtime and power interruptions.
• Self-operating system saves on labor costs because staff can now spend
time solving problems rather than uncovering them.
• Remote monitoring services and on-site equipment evaluation provides
expertise when you need it.
• Display panel shows an output signal proportional to the relative change
in the bushings’ currents due to insulation deterioration, which means users
receive accurate information for both the power factor and capacitance of
the monitored bushing set.
• Multi-function LED is a different color for normal (green), warning (yellow),
and alarm (red), providing instant recognition of the severity of any problem.
• Parameters can be programmed at the panel or remotely through an optional
computer link-up, units are self-diagnosing, and users can pinpoint any
malfunction locally as well as remotely.
• Self-contained unit requires minimum resources and outage time. Comes
standard with NEMA 4 enclosure, diagnostic software, a three- or six-bushing
sensor set, and with an RS-485 Modbus RTU port that allows on-site
communication. The complete package means faster and easier installation.
• Uses the same sensor set to perform online periodic monitoring of partial
discharge (arcing or sparking). That information helps analyze root causes
of internal gassing or other discharge activity related to the winding insulation,
internal connections, bushings, or magnetic core iron.
• Highly sensitive instrumentation can detect PD signals as low as 20-30 pC
even in extremely noisy environments like those in substations or power plants,
which means accurate reports that allow for better decision making.
• Available with a commercial-grade modem for remote communication.