Description
BE1-67 Phase Directional Overcurrent Relays are designed for the protection of transmission and
distribution lines where the direction as well as the magnitude of the fault current (or power flow) is to be
considered in the tripping decision.
BE1-67 relays are directionally controlled, microprocessor based, time overcurrent relays. The directional
element is polarized by the phase-to-phase quadrature voltage of the power system. That is, the
directional element monitoring the phase A current uses the voltage between phases B and C to
determine the direction of current (or power) flow into the fault. Then, if enough current flows in the
tripping direction of the relay, the relay will pickup, time out, and trip. The angle of maximum sensitivity for
the relay is also adjustable to allow the directional characteristic to be matched to the line and system
conditions. Figure 1-1 illustrates the operation of the directional element and defines the terms that are
used in the following discussion.

Figure 1-1a shows the connections to the sensing circuits for a single phase BE1-67. Figure 1-1b
illustrates the phasor quantities monitored by the relay for a unity power factor condition, and for a single
phase fault. Figure 1-1c shows the protected line on an R-X diagram. The angle alpha in Figure 1-1b and
Figure 1-1c are the characteristic angle settings for the relay.
The directional characteristic of the relay is adjustable to allow the relay to be sensitive for phase faults
and to maximize sensitivity at the characteristic angle representing typical power factor.
Twelve standard time-current characteristic curves are available to aid in the coordination of this relay
with other protective devices in the system. These include seven characteristic curves that are standard in
North America and five that are compatible with British or IEC standards requirements. Any of the curves
may be switch selected to suit requirements at the time of installation.
If the supply to the protected portion of the system is constant, and if the magnitude of the fault current is
determined primarily by the location of the fault on the line, the selection of a more inverse time
characteristic is more desirable to provide selective coordination with adjacent line protection. However, if
the capacity of the supply varies significantly over a period (such as a day), a less inverse time or even
the definite time characteristic, may be preferred to provide smoother coordination.
Limited Region of Operation
A limited region-of-operation option is available to provide additional protection against false tripping on
mutually coupled lines. Faults on adjacent lines that share the same poles, towers, or right-of-way may
induce currents on the protected line which appear as fault currents in the tripping direction. The limited
region of operation mode provides discrimination between faults on the protected line and faults on the
adjacent line. To order this option, specify option 3-5 or 3-6.
One consideration in applying a phase directional overcurrent relay is the definition of trip direction. For
most applications, the setting of the relay directional element is based upon the impedance characteristics
of a given circuit. This angle is then used as the maximum torque angle and any current flowing in the
half-plane defined by this angle is considered to be in the trip direction.
However, there are at least two situations where the half-plane trip region is not adequate. They are when
load current approaches the fault current and when leading current flows in the non-trip direction above
the relay pickup setting.
Load Current Approaches Fault Current
Pickup settings on a phase overcurrent device are normally set below the expected fault current levels on
that line by some margin. Consequently, it is possible for load current to approach (or exceed) the pickup
setting on the relay. This could lead to an undesirable trip for an acceptable load condition.
Weak Infeed Condition
During a period of abnormally low system voltage, leading power factor current above relay pickup can
flow in the non-trip direction of a line. Probable current sources are outlying capacitor banks. This could
cause the current to be sensed as lagging current flowing in the trip direction and leading to an
undesirable trip. (A condition often referred to as weak infeed because the lower voltage system - where
load is present - attempts to correct the undervoltage condition on the higher voltage system.)
Application
Without the ability to act on the direction of current flow, it is difficult to coordinate the settings of time
overcurrent relays on lines that interconnect a series of substations. Without this capability, either
undesired tripping of adjacent lines may occur or a fault may go undetected because of the high settings
required by non-directional relays.
With directional time overcurrent relays, the settings and time delays can be decreased and the undesired
tripping eliminated. Figure 1-5 illustrates the use of directional overcurrent relays on a group of
interconnected distribution substations fed from a common source. In this example, non-directional
overcurrent relays (51) are used to protect the lines leaving the supply bus because there is only one
source of fault current. However, the breakers at the load buses (C, D, E, and F) are protected by
directional time overcurrent relays (67) to prevent overtripping in the event of a fault. This will remove the
faulted line and retain service to the connected loads.
In the case where two sources of power can supply fault current, as shown in Figure 1-6. directional
overcurrent relays will need to be applied to each end of the protected lines to prevent undesired tripping.
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved